CHAPTER 3
OPERATION
PR1: 10/18//12 AERCO International Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288
Page 39 of 166
GF-120
OMM-0041 0E
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp
Limit
Hi Temp Limit 130°F
Unit Type
KC Boiler, KC Boiler LN,
BMK Boiler Std, BMK Boiler
LN, BMK Boiler Dual, KC
Water Heater, KC Water
Heater LN, Innovation WH
BMK Boiler
LN
Unit Size
(See
NOTE
at end
of Table 3-4)
750 MBH, 1000 MBH, 1500
MBH, 2000 MBTU, 3000
MBH, 6000 MBH
1500 MBH
(1.5 MBTU)
Fuel Type
Natural Gas, Propane
Natural Gas
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct
Drive or
Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F
Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor
= Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
195°F
195°F
Temp Hi Limit
40°F
210°F
195°F
Max Valve Position
40%
100%
100%
Pump Delay Timer
0 min.
30 min.
0 min.
Pump Delay Timer
0 min.
30 min.
0 min.
Aux Start On Dly
0 sec.
120 sec.
0 sec.