Press the down ▼ arrow key until
CAL Voltage 60%
is displayed.
29.
Press the CHANGE key.
CAL Voltage 60%
will begin to flash.
30.
The oxygen level at the 60% valve position should be as shown below. Also, ensure that
31.
the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.
Table 4-3: Combustion Oxygen Levels for a
60%
Air/Fuel Valve Position
Oxygen
%
± 0.2
Carbon
Monoxide
NOx
6.3 %
<50 ppm
<30 ppm
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
32.
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
Once the oxygen level is within the specified range at 60%, press the ENTER key to
33.
store the selected blower output voltage for the 60% valve position.
Press the ▲ arrow key until
SET Valve Position
appears on the C-MORE display.
34.
Press the CHANGE key.
SET Valve Position
will begin to flash.
35.
Press the ▼ arrow key until the
SET Valve Position
reads
45%
, then press the ENTER
36.
key.
Press the ▼ arrow key until
CAL Voltage 45%
is displayed.
37.
Press the CHANGE key.
CAL Voltage 45%
will begin to flash.
38.
The oxygen level at the 45% valve position should be as shown below. Also, ensure that
39.
the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.
Table 4-4: Combustion Oxygen Levels for a
45%
Air/Fuel Valve Position
Oxygen
%
± 0.2
Carbon
Monoxide
NOx
7.0 %
<50 ppm
<30 ppm
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
40.
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
Once the oxygen level is within the specified range at 45%, press the ENTER key to
41.
store the selected blower output voltage for the 45% valve position.
Press the ▲ arrow key until
SET Valve Position
appears on the C-MORE display.
42.
Press the CHANGE key.
SET Valve Position
will begin to flash.
43.
Press the ▼ arrow key until the
SET Valve Position
reads
30%
, then press the ENTER
44.
key.
Press the ▼ arrow key until
CAL Voltage 30%
is displayed.
45.
Press the CHANGE key.
CAL Voltage 30%
will begin to flash.
46.