Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA
SECTION 4 – MAINTENANCE
Page
38
of
144
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0128_0B
07/17/2017
Ph.: 800-526-0288
4.2 IGNITER-INJECTOR
The igniter-injector (Kit P/N
58023
) is located on the burner plate at the top of the boiler. In
addition to providing the ignition spark required to light the burner, the igniter-injector also
contains a gas injector tube which connects to the staged ignition assembly. Figure 4-1a
through Figure 4-1c shows the complete burner assembly removed from the boiler and indicates
the location of the igniter-injector flame detector and other related components.
Figure 4-1a: BMK 750/1000 Burner Assembly
BLOWER PROOF SWITCH
BLOCKED INLET SWITCH
IGNITER-INJECTOR
AIR/FUEL VALVE
BLOWER
BURNER PLATE
FLAME DETECTOR
O2 SENSOR
BURNER
STAGED IGNITION
ASSEMBLY
STAGED IGNITION
SOLENOID
GAS FLEX HOSE