The Benchmark 2500 and 3000 gas trains (P/N
22244 and 22215)
contain a Valve Proving
device (P/N
24629-2
). This device monitors the gas pressure on both sides of the Actuator. If
the pressure difference falls below a fixed value, indicating the failure of the Actuator or leakage
in the gas line, it triggers the shutdown of the boiler.
Once the problem has been diagnosed and corrected, the Valve Proving device must be reset
by pressing the red Reset switch before the unit is restarted.
PARTIAL FRONT VIEW
YELLOW RUN LIGHT
•
OFF
during normal operation
•
ON
during valve proving operation
•
ON
when unit is not running
RED ALARM LIGHT & RESET SWITCH
•
OFF
during normal operation
•
ON
indicates a leak or Actuator failure
AERCO
International, Inc.
Blauvelt, NY 10913