Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA
SECTION 3 – MODES OF OPERATION
Page
34
of
144
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0128_0B
07/17/2017
Ph.: 800-526-0288
3.6 AERCO CONTROL SYSTEM (ACS)
NOTE:
ACS is for installations with 9 or more boilers. It utilizes only RS-485 signaling to the boiler.
Installations with 1 to 8 boilers can use Boiler Sequencing Technology (BST), as described in
Section 6 of the
Benchmark 750 – 3000 Boiler Installation and Startup Guide Guide
, OMM-
0127 (GF-205-K).
The ACS mode of operation is used in conjunction with an AERCO Control System. The ACS
mode is used when it is desired to operate multiple units in the most efficient manner possible.
For this mode of operation, an ACS Header Sensor must be installed
between 2 and 10 feet
(0.61 and 3m)
downstream of the
LAST
boiler in the boiler plant's supply water header. The
ACS can control up to 40 boilers; Up to 32 via Modbus (RS-485) network communication. For
ACS programming, operation, and Header Sensor installation details, see ACS Operations
Guide, GF-131. For operation via an RS-485 Modbus network, refer to Modbus Communication
Manual GF-114. To enable the ACS mode, you must set menu items
Boiler Mode
and
Remote
Signal
in the
Configuration
menu as follows:
TABLE 3-4: ACS Mode Settings
MENU OPTION
SETTING
Boiler Mode
Direct Drive
Remote Signal
Network (RS485)
Refer to Section 2.3:
C-More Controller Menus
for instructions on changing menu options.
3.6.1 ACS External Field Wiring
Wiring connections for RS-485 Modbus control are made between the 485 A- and 485 B+
terminals on the ACS (boilers 9 through 40) and the RS-485 COMM terminals in the I/O Box on
the front of the boilers.
Wire the units using shielded twisted pair wire between 18 and 22 AWG. Observe the proper
polarity for the ACS RS-485 COMM wiring connections. Shields should be terminated only at
the ACS and the boiler end must be left floating. Each unit’s wiring must conform to the above.
3.6.2 ACS Setup and Startup
This mode of operation is factory preset and the ACS controls the firing rate (air/fuel valve %
open position). There are no setup instructions for each individual unit.
To operate the unit in MANUAL mode, press the
AUTO/MAN
switch. The REMOTE LED will go
off and the MANUAL LED will light
To change back to the ACS mode, simply press the
AUTO/MAN
switch. The REMOTE LED will
again light and the MANUAL LED will go off.