Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA
SECTION 2: OPERATION
Page
22
of
144
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0128_0B
07/17/2017
Ph.: 800-526-0288
2.8.2 BMK 1500/2000 COMBUSTION CAL Menus
TABLE 2-7a: COMBUSTION CAL Menu: BMK 1500/2000
MENU ITEM DISPLAY
MINIMUM
MAXIMUM
DEFAULTS
BMK 1500
BMK 2000
1
CAL Voltage 16%
0.25
10.00
1.80
–
CAL Voltage 18%
–
1.40
2
CAL Voltage 30%
0.25
10.00
2.30
3.80
3
CAL Voltage 40%
0.25
10.00
2.50
4.30
4
CAL Voltage 50%
0.25
10.00
2.90
5.40
5
CAL Voltage 70%
0.25
10.00
3.80
6.40
6
CAL Voltage 100%
0.25
10.00
7.90
9.50
7
SET Valve Position
0%
100%
Variable
8
Blower Output
Displays current value
9
Set Stdby Volt
0
10.00 V
2.00 V
2.00 V
10
Oxygen Level
Displays current value
2.8.3 BMK 2500/3000 COMBUSTION CAL Menus
TABLE 2-8a: COMBUSTION CAL Menu: BMK 2500/3000
MENU ITEM DISPLAY
MINIMUM
MAXIMUM
DEFAULTS
BMK 2500
BMK 3000
1
CAL Voltage 16%
0.25
10.00
2.20
–
CAL Voltage 14%
–
2.80
2
CAL Voltage 30%
0.25
10.00
4.10
4.60
3
CAL Voltage 40%
0.25
10.00
4.80
5.00
4
CAL Voltage 50%
0.25
10.00
5.30
5.50
5
CAL Voltage 70%
0.25
10.00
6.80
6.90
6
CAL Voltage 100%
0.25
10.00
8.50
9.10
7
SET Valve Position
0%
100%
Variable
8
Blower Output
Displays current value
9
Set Stdby Volt
0
10.00 V
2.00 V
2.00 V
10
Oxygen Level
Displays current value