6 commIssIoNINg
6.1 Setting Fan speed
The speed of the unit can be adjusted during installation according to required ventilation rate.
Figure 6.a
below shows performance curves (for supply air and extract air) at different settings of the 0-10V signal to the motors. Airflow and consumption
refer to one single motor.
Table 6.b
indicates the efficiency of the heat exchanger and of the condensation produced in different climatic conditions, to help the installer or the designer
of the ventilation system to decide if to connect one or both condensation drainages.
High production of condensation is the direct consequence of a high efficiency level as well as of the humidity rate.
Table 6.c
indicates the sound level at the different speed.
Table
6.b
Thermal efficiency of the heat exchanger and average production of condensation water. Data supplied by the manufacturer of the heat exchanger.
The heat exchanger is tested at the University of Luzern (Hochschule Lezern).
EXTERNAL
INTERNAL
Fig. 6.a
Intake curve according to Reg. 1253/2014
Static Pressure - Pa
Airflow - m
3
/h
0
50
100
150
200
250
300
350
400
450
500
550
0
20
40
60
80
100
120
140
160
180
200
220
240
I
II
III
IV
V
VI
A
B
C
D
E
F
G
curve
speed
%
W
max
m
3
/h
max
A (min)
20
10
29
B
37
16
72
C
53
28
114
D
59
35
131
E
69
48
158
F
84
75
198
G (max)
100
105
233
Working point
W
m
3
/h
sPI (W/m
3
/h)
ɳt %
(1)
I
12
54
0,222
88
II
17,4
76
0,230
86
III
25,6
97
0,263
85
IV
36,7
119
0,309
84
V
50,7
140
0,361
82
VI
70
162
0,432
81
(1)
Termal efficiency of the unit.