20
Digital Transformer Ratiometer DTR
®
Model 8510
• In order to write the Present Nameplate value, you must press
ENTER
until
Setup Nameplate
is displayed. Otherwise, the ratio
will not be entered. If the up/down arrows are pressed after
setting the ratio, then it performs a cancel operation and the
changes will not be saved.
REMEMBER:
In order to move one level up and return to
Configure
Instrument
, press the
▼ ▲
keys simultaneously.
4.3.3 Select Test Type
1.
From the top level of
Configure Instrument
, press the ▼ or ▲ key until
Select Test Type
appears on the display, then press
ENTER.
Figure 4-14
2.
Select
VT/PT
or
CT
using ▼ or ▲ and press
ENTER
. The display will
return to
Select Test Type
.
NOTE:
Once the Test Type is selected, it is retained until changed by the
user. If the instrument is turned OFF and turned ON, the Test Type will be
the same as last selected.
4.3.4 Select Test Mode
1.
From the top level of
Configure Instrument
, press the ▼ or ▲ key until
Select Test Mode
appears on the display, then press
ENTER.
Figure 4-15
2.
Select
Ratio
or
CONT/Ratio
test using ▼ or ▲ and press
ENTER
. The
display will return to
Select Test Mode
.