8
Clamp-on Meter Model 514
CHAPTER 3
SPECIFICATIONS
3.1 Electrical Specifications
Reference Conditions:
23°C ±5°C, 45 to 80% RH, True RMS for V
AC
and
A
AC
accuracy are specified from 5% to 100% of range, crest factor 1.4 < CF
< 3 at full scale & CF < 6 at half scale.
AC Amperes
(Auto-Ranging)
Range
Resolution
Accuracy
Overload
40A
0.01A
50/60Hz: 1.9% of Reading ± 5cts
60/500Hz: 2.5% of Reading ± 5cts
1200Arms
400A
0.1A
1000A
1A
AC Volts
(Auto-Ranging)
Range
Resolution
Accuracy (50/500Hz)
Overload
400V
0.1V
1.5% of Reading ± 5cts
1000Vrms
750V
1V
DC Amperes
(Auto-Ranging)
Range
Resolution
Accuracy (50/500Hz)
Overload
40A
0.01A
2.5% of Reading ± 10cts
1200Arms
400A
0.1A
1000A
1A
DC Volts
(Auto-Ranging)
Range
Resolution
Accuracy (50/500Hz)
Overload
400V
0.1V
1.0% Reading ± 2cts
1000Vrms
1000V
1V
Summary of Contents for 2117.70