![AEG Protect D 10000 LCD User Manual Download Page 14](http://html.mh-extra.com/html/aeg/protect-d-10000-lcd/protect-d-10000-lcd_user-manual_14769014.webp)
14
ENVIRONMENTAL AND SAFETY
Certifications
EN 62040-1
IEC/EN 62040-2: Cat. C3
IEC/EN 62040-3
EN 60950-1
EMC (Emissions)*
Conduction C3 IEC/EN 62040-2
Radiation C3 IEC/EN 62040-2
EMC (Immunity)
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on
signal ports), IEC 61000-4-5, Level 4,
Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
Agency markings
CE
Operating temperature
0~40
℃
full load no derating
40~50
℃
output power derating to
50% load, Charger current derating
50%
Storage temperature
-15 to 40°C (32 to 104°F) with
batteries
-25 to 60°C (5 to 140°F) without
batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing
Operating altitude
Up to 3,000 meters (9,843 ft) above
sea level with 10% derating per
1000m
Transit altitude
Up to 10,000 meters (32,808 ft)
above sea level
Audible noise
< 50 dBA at 1 meter typical for 6kVA
models
< 55 dBA at 1 meter typical for
10kVA models
NOTE: *
for output cable < 10m.