User Manual
A Technical Specifications
29
A.2 6kVA(L)
,
10kVA (/B)
Model
Index
6kVA(L)
10kVA(/B)
In
p
ut
Voltage range (V)
When the voltage within the range of 176Vac
~
275Vac, the UPS
can bear 100% full load;
When the voltage within the range of 80Vac~176Vac, the load
carrying capacity linear decreases according to the input voltage
amplitude.
Frequency range (Hz)
50/60±10%(50/60 self-adaption)
Input way
Sine-wave
Battery voltage (V)
192 (default) (can be set to 12~20 cells *12V by communication)
O
u
tp
u
t
Capacity (VA/W)
6000/5400
10000/9000
Voltage (V)
220±2% (default) (can be set to 208/220/230/240)
Frequency (Hz)
50/60±0.2% (battery mode)
Wave form
Sine-wave
Voltage distortion
THD <1% (linear load); THD<4%(non-linear load)
Power factor
0.9 (at the room temperature, the power factor can be 1.0, and the
UPS can carry load normally)
Transfer time (ms)
0
O
ve
rlo
a
d c
ap
a
cit
y
Low overload for
10min
6900VA/6210W
<
Load≤7800VA/7020W
11500VA/10350W
<
Load≤13000VA/11700W
Medium overload for
30s
7800VA/7020W
<
Load≤9000VA/8100W
13000VA/11700W
<
Load≤15000VA/13500W
Heavy overload for
500ms
Load
>
9000VA/8100W
Load
>
15000VA/13500W
M
e
ch
an
ic
a
l
p
ar
t
Size (W×D×H) (mm)
438×500×86
Weight(kg)
10.6
12.2