User Manual
A Technical Specifications
27
Model
Index
1kVA
1kVA(L)
2kVA
2kVA(L)
3kVA
3kVA(L)
O
ve
rlo
a
d
c
ap
a
cit
y
Low overload
for 1min
1000VA/900W
<
Load≤1300VA/1040W
2000VA/1800W
<
Load≤2600VA/2080W
3000VA/2700W
<
Load≤3900VA/3120W
Medium
overload for
1s
1300VA/1040W
<
Load≤1500VA/1200W
2600VA/2080W
<
Load≤3000VA/2400W
3900VA/3120W
<
Load≤4500VA/3600W
Heavy
overload for
200ms
Load
>
1500VA/1200W
Load
>
3000VA/2400W
Load
>
4500VA/3600W
O
th
e
rs
Backup time
With full
load for
3min
Long
backup
time
Can
be
configured
any
backup
time
according
to needs
With full
load for
3min
Long
backup
time
Can be
configured
any
backup
time
according
to needs
With full
load for
3min
Long
backup
time
Can be
configured
any
backup
time
according
to needs
Charge
recovery
time
For standard model, the charge recovery time is less than 10 hours. For
long backup model, the charge recovery time is determined by the
capacity of external battery pack.
Communication
interface
Equips RS232 port to support UPS power management software
Panel display
LCD shows the running status of the UPS
Alarm function
Alarm for battery low-voltage, mains abnormal, UPS fault, output overload.
Protection function
Protect for battery under-voltage, overload, short-circuit, over-
temperature, input over-voltage
Noise (dB)
<50
<55