10
•
04: ECO enable/disable
Interface
Setting
ENA: ECO mode enable
DIS: ECO mode disable
•
05: ECO voltage range setting
Interface
Setting
Press the Down key or Up key to set the acceptable
high voltage point and acceptable low voltage point:
HLS: High loss voltage in ECO mode
(For
208/220/230/240 VAC models, the setting range is
from +7V to +24V of the nominal voltage. For
110/115/120/127 VAC models, the setting range is
from +3V to +12V of the nominal voltage).
LLS: Low loss voltage in ECO mode (For
208/220/230/240 VAC models, the setting range is
from -7V to -24V of the nominal voltage. For
110/115/120/127 VAC models, the setting voltage is
from -3V to -12V of the nominal voltage)
•
06: Bypass enable/disable when UPS is off
Interface
Setting
ENA: Bypass enable
DIS: Bypass disable
•
07: Bypass voltage range setting
Interface
Setting
Press the Down key or Up key to set the acceptable
high voltage point and acceptable low voltage point:
HLS: Bypass high voltage point
LLS: Bypass low voltage point
For 208/220/230/240 VAC models:
230-264: setting the high voltage point from 220Vac to
264Vac
170-220: setting the low voltage point from 170Vac to
220Vac
For 110/115/120/127 VAC models:
120-140: setting the high voltage point from 120Vac to
140Vac
85-115: setting the low voltage point from 85Vac to
115Vac
Summary of Contents for TOPV 1500
Page 19: ...18 APPLY administrator...
Page 20: ...19 Next Open Monitor...
Page 21: ...20 1 2 Install...
Page 22: ...21 ViewPower ViewPower...
Page 23: ...22 EP 28 43 14 1 2 3 4 11 12 13 41...
Page 24: ...23...
Page 28: ...27 4 10 ENA DIS ESC HLS LLS BAT CF EP EPO FA TP CH 3 1 8 1 2 3 4 5 6 7 8 1 2 3...
Page 29: ...28 H M S Vac Vdc Hz 0 25 26 50 51 75 76 100 4 Bypass 4 0 25 26 50 51 75 76 100 Vac Vdc Hz...
Page 30: ...29 ON Mute Button 2 5 OFF Enter Button 2 Select Button 10 5 5...
Page 31: ...30 Top Vision 24 03 9000 940 03 9000900 03 9027444 10 48091...