PCI-1736UP User Manual
26
3.3.1 Isolated Digital Inputs
Each of the 16 isolated digital input channels accept voltages from 5 to 30
V. Every eight input channels share one external ground.
(Channels 0~7 use EI.WCOM1 (Wet Contact) and EI.DCOM1 (Dry Con-
tact). Channels 8~15 use EI.WCOM2 (Wet Contact) and EI.DCOM2
(Dry Contact).) The following figure shows how to connect an external
input source to the card's isolated inputs.
Figure 3.3: Isolated Digital Input Connection
Figure 3.4: Bi-directional Isolated Digital Input Connection
Summary of Contents for PCI-1736UP
Page 1: ...PCI 1736UP 32 channel Isolated Digital Input Output Card User Manual...
Page 34: ...PCI 1736UP User Manual 28...
Page 35: ...2 APPENDIX A Specifications...
Page 38: ...PCI 1736UP User Manual 32...
Page 39: ...2 APPENDIX B Block Diagram...
Page 40: ...PCI 1736UP User Manual 34 Appendix B Block Diagram Figure B 1 PCI 1736UP Block Diagram...
Page 41: ...2 APPENDIX C Register Structure and Format...
Page 48: ...PCI 1736UP User Manual 42...