55
APAX-5000 I/O Series User Manual
Chapter 3
D
igital Input
/Output
Modules
APAX-5060 Specifications
Relay Output
Channels:
12
Relay Type:
Form A (SPST)
Switching Capacity and Lifetime of the Contact (For Resistive Load)
–
VDE: 30,000 operations (5 A @ 250 VAC, 10 operations/minute at 8
C)
70,000 operations (5 A @ 30 VDC, 10 operations/ minute at 85
C)
–
UL: 60,000 operations (5 A @ 250 VAC)
100,000 operations (5 A @ 30 VDC)
–
Mechanism: 20,000,000 operations (no load, 300 operations/minute)
Breakdown Voltage:
500 VAC (50/60 Hz)
Contact Resistance:
30 m
(maximum)
Insulation Resistance:
1 G
(minimum) at 500 VDC
Operating Time:
10 ms maximum at rated voltage (excluding bounce time)
Release Time:
5 ms maximum at rated voltage (excluding bounce time)
Protection
Isolation:
2,500 VDC (Between channels and backplane bus)
Fail Safe Protection*
* When I/O module lose its communication with controller or coupler, the output chan-
nel will generate a pre-defined value
Environment
Operating Temperature:
-10 ~ 60
C (when mounted vertically)
Storage Temperature:
-40 ~ 70
C
Relative Humidity:
5 ~ 95% (non-condensing)
General
Dimensions (W x H x D):
30 x 139 x 100 mm
Weight:
195 g
Power Consumption:
2 W @ 24 VDC (typical)
Status Display:
LED per channel
–
On:
Logic level “1”
–
Off:
Logic level “0”
Summary of Contents for APAX-5013
Page 1: ...User Manual APAX 5000 Series I O Modules...
Page 8: ...APAX 5000 I O Series User Manual viii...
Page 9: ...Chapter 1 1 Overview...
Page 23: ...15 APAX 5000 I O Series User Manual Chapter 1 Overview...
Page 33: ...Chapter 2 2 Analog Input Output Modules...
Page 49: ...Chapter 3 3 Digital Input Output Modules...
Page 116: ...APAX 5000 I O Series User Manual 108...
Page 117: ...Chapter 4 4 Backplane Modules...
Page 120: ...APAX 5000 I O Series User Manual 112...
Page 121: ...Chapter 5 5 Power Supply Modules...
Page 124: ...APAX 5000 I O Series User Manual 116...