Glycol Chillers : BC Series with MG Control Instrument
Page: 38
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
2.
Use the Up and Down arrow keys to select the address for this unit. The factory
default is 1. The selection range is from 1 - 10.
3.
Press the Select button to save the address and confirm success.
3.8 INSTRUMENT : FLOW MENU (Option)
A.
The Flow Menu is only functional when the optional flow meter is installed. Items in the
Flow Menu are Enable, Offset and Calibration.
B.
Advance to the Flow Enable / Disable screen. Select Enabled to enable the flow option.
C. Offset. This allows the user to select the flow offset according to the pump horsepower.
1.
These values should be factory set and should not be changed. Adjust only if
they are set to values other than the factory default.
D.
Calibration. This allows the user to calibrate the unit’s flow meter.
1.
Using a reliable and accurate external flow meter the user can input a calibration
constant value in the screen so that the unit flow display matches the external
flow meter.
2
Use the Up or Down arrow keys to input the value and then press the Select
button to save and confirm success.
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Main Menu
Setpoints
Utilities
Network
Flow
Options
Machine
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Main Menu
Setpoints
Utilities
Network
Flow
Options
Machine
Back
Pick
Go
FLow
Enable
Offset
Calibration
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Flow
Enable
Disable
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Flow
Enable
Offset
Calibration
Back
Pick
Go
FLow
Enable
Offset
Calibration
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Flow Enable
Success
Acknowledge
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Offset
-3 GPM
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Flow
Enable
Offset
Calibration
Back
Pick
Go
FLow
Enable
Offset
Calibration
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Offset
Success
Acknowledge
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Calibration
770
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Flow
Enable
Offset
Calibration
Back
Pick
Go
FLow
Enable
Offset
Calibration
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Calibration
Success
Acknowledge