Glycol Chillers : BC Series with MG Control Instrument
Page: 35
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
D.
Lo Deviation. The Lo Deviation value programs the controller to sound the alarm if the
process temperature exceeds the set difference from setpoint. For example, Lo Deviation
= 10°F, Setpoint = 50°F. Lo deviation alarm will sound if the temperature cools to 40°F.
1.
The factory default is 10°. The range for the Lo Deviation is from 0°F - 50°F.
2.
With set points above 50°F, the maximum Lo Deviation setting should be no more
than 100°F minus set point. For example, with a 70°F set point the Lo Deviation
should not be set more than 30°F.
3.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
D.
Low Flow (optional feature not included on all units). The Low Flow value programs
the controller to sound an alarm if the process flow goes below the low flow set value.
For example, if the flow set value is 3 GPM and if the flow goes below 3 GPM an alarm
condition is indicated. Note: the low flow alarm feature is only available with the purchase
of the optional flow meter.
1.
The factory default is 0 GPM. The range for the Low Flow is from 0 to 100 GPM.
2.
Once acknowledged, press the Back button repeatedly to return to the Setpoints
screen or press the home button to return to the Home screen.
3.6 Instrument : Utilities menu
A.
Items in the Utilities menu include the operations for the Software Version, Display Test
and Sensor Display.
B.
Software Version. The software version number is the current version of the controller’s
software. This number can be useful when troubleshooting at times.
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Low Flow
Cancel
Adjust
OK
Setpoints
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
Back
Pick
Go
3 GPM
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Low Flow
Success
Acknowledge
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Change Setting
Lo Deviation
Success
Acknowledge
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Software Version
Back
c239192b31f8605a4be3f
3070525d514621a4ae8
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Setpoints
Process Setpoint
Hi Deviation
Lo Deviation
Low Flow
Back
Pick
Go
Utilities
Software Version
Display Test
Sensor Display
Back
Pick
Go
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
To Process
S e t p o i n t : 5 0 ° F
C i r c u l a t i n g
50°F
Main Menu
Setpoints
Utilities
Network
Flow
Options
Machine
Back
Pick
Go
Utilities
Software Version
Display Test
Sensor Display
Back
Pick
Go