14
-- LEVEL SET --
LEVEL ONE ENABLED
LEVEL ONE DISABLED
LEVEL ONE:
NO PUMP
LEVEL ONE: PUMP OK
LEVEL TWO ENABLED
LEVEL TWO DISABLED
LEVEL TWO:
NO PUMP
LEVEL TWO: PUMP OK
LEVEL THREE ENABLED
LEVEL THREE DISABLED
LEVEL THREE:
NO PUMP
LEVEL THREE: PUMP OK
LEVEL FOUR ENABLED
LEVEL FOUR DISABLED
LEVEL FOUR:
NO PUMP
LEVEL FOUR: PUMP OK
Return to LEVEL SET screen
LEVEL SET
LEVEL ENABLE -
Enable and Disable options allow
for the activation or deactivation of the control logic
that governs the input of the level wand(s). Up to four
level wands can be used simultaneously.
LEVEL: PUMP -
Each level wand, in the Enabled
state, can be used to control the high voltage relay
output(s) of the controller.
When the “No Pump” option is selected, by pressing
ENTER on the keypad, the high voltage relay output(s)
will deactivate upon the level wand being triggered.
When the “Pump OK” option is selected, by pressing
ENTER on the keypad, the high voltage relay output(s)
will not deactivate upon the level wand being triggered
but an alarm message will appear on the display of the
controller that reads: Possible Dry Pump.
Note:
Levels 2, 3 and 4 are a built in function of the
MicroTron control platform. Not used on glycol feeder
models.
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER