Rack Mounting the NetVanta 1131
The NetVanta 1131 can be installed into a 19-inch equipment rack by following these steps:
•
The NetVanta 1131 is intended to be installed, maintained, and serviced by qualified
service personnel only and is for use with NetVanta switches only.
•
If installed in a closed or multi-unit rack assembly, the operating ambient temperature
of the rack environment may be greater than room ambient temperature. Therefore,
consideration should be given to installing the equipment in an environment
compatible with the maximum specified 50°C ambient temperature.
•
Installation of the equipment in a rack should be such that the amount of air flow
required for safe operation of the equipment is not compromised.
•
Be careful not to compromise the stability of the equipment mounting rack when
installing this product.
•
Consideration should be given to the connection of the equipment to the supply circuit
and the effect that overloading the circuit might have on overcurrent protection and
supply wiring. Appropriate consideration of equipment nameplate ratings should be
used when addressing this concern.
•
Reliable grounding of rack-mounted equipment should be maintained. Particular
attention should be given to supply connections other than direct connections to the
branch circuit (e.g., use of power strips).
•
This equipment incorporates double pole/neutral fusing. If the neutral fuse opens and
the line fuse does not open, voltage could still be present in the unit. Line and neutral
are provided with fuses for overcurrent protection.