28
4.1.9.5 Running Hour Reset
• Reset the running hour.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter running hour reset setting.
2. Use UP and DOWN key to select “YES” for clear or “NO” for leave.
3. Press ENTER key to finish setting and return to the previous menu.
※ Press LEFT key to cancel input and return to the previous menu.
※ The running hour starts accumulating when the current input value exceeds 1% of the
rated value.
4.1.10 Demand
4.1.11 Input/Output
4.1.10.1 Mode
4.1.11.1 Digital Input
4.1.10.2 Period
• Demand calculation mode setting. The selectable mode are sliding block, fixed block,
The default value is sliding block.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter demand mode setting.
2. Use UP and DOWN key to select demand mode.
3. Press ENTER key to finish setting and return to the previous menu.
※ Press LEFT key to cancel input and return to the previous menu.
• The meter has two digital input uncluding DI1, DI2.
• In addition to being Digital Input, the functions of the digital input port can also be set up
as: Demand Reset, MAX Demand Reset, Energy Reset, MAX/MIN Reset, Relay Reset.
The default value is DI.
• Trigger level can be set to ON or OFF.
• The input debounce time can be set. To avoid misoperation, the set range is 0~99 (x
• Calculation period time setting. The setting range is 1 ~ 60 minutes. The default value is
15 minutes.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter period setting.
2. Press UP or DOWN key to select the numeric.
3. Press LEFT key move to the next digit.
4. Repeat step 2 to 3 until finishing 2-digits setting of period time, press ENTER key to
save and return to the previous menu.
※ Press LEFT key to cancel the setting and return to the previous menu.