4.1.6 Communction
Firstly, select the port to be set, including COM1, COM2.
4.1.6.1 Address
• Power meter device address setting. The selectable range is 1~247. Broadcast is 255.
The factory value is 1.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter address setting.
2. Press UP or DOWN key to select the address.
3. Press LEFT key and move on to the next digit.
4. Repeat step 2 to 3 until finishing 3-digit setting of communication device address,
press ENTER key to save and return to the menu.
※ Press LEFT key for 2 seconds to cancel the setting and return to the previous menu.
6. Press UP or DOWN key to select the corresponding circuit of the circuit.
7. Press ENTER key to finish setting and return to the previous menu.
8. Press ENTER key to enter user-defined page setting.
9. Press UP or DOWN key to select the parameter position to be set, press ENTER key to
enter.
10. Press UP or DOWN key to select the parameter to be displayed at that position.
11. Press ENTER key to finish setting and return to the previous menu.
12. Press ENTER key to enter screen rotation time setting.
13. Press LEFT key and move on to the next digit.
14. Press LEFT key move to next digit of second time.
15. Repeat step 13 finishing second time setting, press ENTER key to save and return to
the menu.
※ Press LEFT key for 2 seconds to cancel the changes and return to the previous menu.
4.1.6.2 Baudrate
• Baud rate setting. The selectable range is 1200、2400、4800、9600、19200、38400、
57600、115200 bps. The factory value is 9600 bps.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter baud rate.
2. Use UP and DOWN key to select required baud rate.
3. Press ENTER key to finish setting and return to the menu.
※ Press LEFT key to cancel the setting and return to the previous menu.