21
4.1.5.3 Current Transformer Setting
• CT Primary: The setting range of Ampere of CT primary side is 5~9999 A. The default
value is 5 A.
• CT Secondary: The setting range of Ampere of CT primary side is 1 A or 5 A. The default
value is 5 A.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter the CT primary.
2. Press UP or DOWN key to select the loop to be set, press ENTER key to enter.
3. Press UP or DOWN key to select the numeric.
4. Press LEFT key move to the next digit.
5. Repeat step 3 to 4 until finishing ampere setting, press ENTER key to save and return
to the previous menu.
4.1.5.2 Voltage Transformer Setting
• PT Primary: The setting range for the volt of PT primary side is 0~9999k V. The default
value is 600 V.
• PT Secondary: The setting range for the volt of PT primary side is 50~600 V. The default
value is 600 V.
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter the volt of PT primary setting.
2. Press UP or DOWN key to select and set the voltage value of loop A or loop B or the
voltage unit of the PT primary, and press the ENTER key to enter.
3. Press UP or DOWN key to select the numeric.
4. Press LEFT key to move to the next digit.
5. Repeat step 3 to 4 until finishing volt setting, press ENTER key to save and return to
the previous menu.
6. Press ENTER key to enter the voltage unit setting.
7. Press UP or DOWN key to select the unit V or kV.
8. Press ENTER key to save and return to the menu.
9. The volt setting of PT secondary is the same as PT primary.
※ Press LEFT key to cancel input and return to the previous menu.
Voltage phase/line
input
Sub loop set up
1P2W
1P3W
3P3W
3P4W
1P2W
○
X
X
X
1P3W
○
○
X
X
3P3W
○
X
○
X
3P4W
○
X
○
○
※ Each group of loops can independently set the phase-line system for measurement,
but there will be restrictions based on the voltage phase-line system connected to the
main loop, see the table below: