20
4.1.4 USER PASSWORD
• When entering the parameters settings or clear & reset the pages both need to enter
password. The factory value is 1000.
• Steps of setup are as follows:
1. Press UP or DOWN key to select the first digit of the user password.
2. Press LEFT key, move to the next digit of the user password.
3. Repeat step 1 to 2 until finishing the 4-digit of the user password.
4. After entering the 4th digit of the user password, press ENTER key to enter meter
parameter setting.
※ If type error, the number can be re-entered after 4 zeros.
※ If you need to exit the user password page, press and hold the LEFT key for 2
seconds back to default page.
4.1.5 General
4.1.5.1 Wire System
• Power System:The wire system can be selected with single-phase two-wire (1P2W),
single-phase three-wire (1P3W), three-phase three-wire 1CT (3P3W1CT), three-phase
three- wire 2CT (3P3W2CT), three-phase three-wire 3CT (3P3W3CT), three-phase four-
wire 1CT (3P4W1CT), three-phase Four-wire 3CT (3P4W3CT), The factory value is three-
phase four-wire 3CT (3P4W3CT),
• Steps of setup are as follows:
1. Press ENTER key on the menu page to enter wire system setting.
2. Press UP or DOWN key to select the loop to be set and press ENTER to enter.
3. Press UP or DOWN to select the wire system method.
4. Press ENTER key to finish setting and return to the previous menu.
※ Press LEFT key to cancel the setting and return to the previous menu.
4.1.3 Power Meter Info Search
Press ENTER key enter the system menu and select Information then press ENTER key to
enter.
Press LEFT key return to previous page.
• Power Loop including: Power phase, PT Primary/Secondary value, CT Primary/Secondary
value, energy unit, branch loop voltage assign. Depending on the attributes of the main
loop and the sub-loop, the displayed content is different.
• Communication including: COM1, COM2, other communication interface.
• Meter Information including: Device , Sub-A Loop, Sub-B Loop