background image

IRIS-4 160

 

Quick Installation and

Maintenance Guide

IRIS-4 160

13

12

For a reliable 4G/3G/2G connection it is recom-
mended that for the chosen network (SIM card) used 
there should be at least two base stations with signal 
strength (CSQ ) of 10 or more .

If the signal strength is below or close to minimum 
then try to reposition the IRIS-4 160 or use an exter-
nal building or high gain antenna (if necessary), and 
rerun the network scan to check signal strength .
Once you have the required 4G/3G/2G signal 
strength power down the dialler and insert the SIM 
card into the SIM card holder .

Insert the 4 x AA batteries if required
and power the dialler back up.

Now press the button labelled AP again and on the 
connection device connect to the ‘IRIS’ network and 
using the web browser connect to the IRIS-4 160 web 
interface again by browsing to ‘iris .local’ .
Enter in the installer code setup beforehand and then 
select the Installation Wizard as indicated next .

IRIS-4 160 not using 4g/3g/2g or using 

ethernet/Wi-Fi after network scan completed: 

Installation Wizard

Select the Installation Wizard and follow the on 
screen prompts . 

Note 1: If installing the IRIS-4 160 without batteries 
then please untick the ‘Use battery backup’ option.

Note 2: During the Installation Wizard the Wi-Fi 
status screen and the signal strength will be 
displayed. For a reliable Wi-Fi connection it is 
recommended that the Wi-Fi network used should 
have a signal strength of 20 or more. If this signal 
strength is lower than suggested try moving the 
IRIS-4 160 nearer the Wi-Fi router.

Once Installation Wizard is completed and any 
additional panel interface configuration setup via 
the settings menu, check/configure the panel for 
the connection method being used and the current 
battery status .

IRIS-4 160 using 4g/3g/2g connection:

4G/3G/2G Network Scan

Select the ‘4G/3G/2G network scan’ .
The scan must be carried out without the SIM card 
fitted . The dialler listens for every base station in 
range, requests operator name and records the signal 
strength . This will take a few minutes to complete . 

To check the current battery status go to the option 
‘Battery status’ in the main menu and this will indi-
cate the current status of the batteries .
Please go into the ‘Battery status’ option and confirm 
that the Health status is showing as “Good” before 
leaving site, as shown:
 

This will take a few minutes to complete.

Summary of Contents for IRIS-4 160

Page 1: ...AIRBORNE DC MEDIUM Hurtigmanual Snabbguide IRIS 4 160 Quick Installation and Maintenance Guide...

Page 2: ...mission System ATS configuration up to SP3 for single path or ATS configuration DP2 for dual path The IRIS 4 160 is based on the successful IRIS Touch NG range of AoIP diallers with the same hardware...

Page 3: ...en the following information will not be required as it will be assigned by the network IP address Gateway address Subnet mask address Wi Fi Connection Details The customer s Wi Fi network details are...

Page 4: ...tened or other activities such as alarm alerting by the panel at regular intervals If batteries are required DO NOT FIT until indicated in Section 6 9 Configuration Use Batteries approved to IEC61951...

Page 5: ...s the equivalent restore signal Via Sense Resistors It is also possible to link the contacts to the IRIS 4 160 dialler via sense resistors so that an open or short circuit tamper on the loop is detect...

Page 6: ...local Configuration viaWeb Browser usingWi Fi Connection Can be configured using the Wi Fi connection using a standard Web browser from any smartphone tablet or laptop device and supports the followin...

Page 7: ...and follow the on screen prompts Note 1 If installing the IRIS 4 160 without batteries then please untick the Use battery backup option Note 2 During the Installation Wizard the Wi Fi status screen a...

Page 8: ...heck battery status and replace if below required level Reflash IRIS 4 160 software to latest version Test the configured communication paths Ethernet Wi Fi 4G 3G 2G Perform full test of alarms from t...

Page 9: ...atteries fitted for backup purpose replaced them every two years 7 4 Check SoftwareVersion Reflash Go to the settings menu and then select Latest software this will then check with the AddSecure Refla...

Page 10: ...up impedance 10K to 3 3V supply Alarm protocols SIA level 1 to 3 reference SIA DC 03 1990 01 R2003 10 Contact ID reference SIA DC 05 1999 09 Fast format Scancom for dial capture and serial connection...

Page 11: ...s are connected to avoid safety hazards SELV SELV Safety Extra Low Voltage is defined as a secondary circuit which is so designed and protected that under normal and single fault conditions the voltag...

Reviews: