Adaptive® JUNIOR – Technical and HMI User Guide
REV 1.04
27
46=1, 54=2, 62=3
Integer
See Table 10
Fan (x) alarm enables
63
Integer
Fan PSU supply voltage setting
0 = Off – use voltage in supply
1 = 5V
2 = 12V
3 = 24V
64
Integer
See Table 11
Current fan alarm status
65=A, 66=B, 67=C, 68=D
Floating point
Read only
Temperature sensor (x) value
69=1, 72=2, 75=3
Floating point
Read only
Fan (x) current value
70=1, 73=2, 76=3
Floating point
Read only
Fan (x) voltage value
71=1, 74=2, 77=3
Integer
Read only
Fan (x) speed
78
Floating point
Read only
Bridge voltage (TEC) value
79
Floating point
Read only
Current monitoring voltage
80
Floating point
Read only
Bridge current (TEC) value
82
Integer
Read only
Current PWM output value
83
Floating point
Read only
Supply voltage value
84
Floating point
Read only
On board potentiometer reading
90=A, 92=B, 94=C, 96=D
Floating point
Calibration gain for sensor (x)
91=A, 93=B, 95=C, 97=D
Floating point
Calibration offset for sensor (x)
Table 7 Status bit details
Bit = 1 indicates condition is active
Table 8 Bit arrangement for alarm enable, relay and shutdown registers
Sensor
Sensor D
Sensor C
Sensor B
Sensor A
Alarm type High Low High Low High Low High Low
Bit number 7
6
5
4
3
2
1
0
Bit = 0 disabled, Bit = 1 enabled
Table 9 Temperature alarm status bits
Sensor
Sensor D
Sensor C
Sensor B
Sensor A
Alarm type High Low High Low High Low High Low
Bit number 7
6
5
4
3
2
1
0
Bit = 1 indicates alarm condition is active
Bit number
Status (1 = alarm active)
0
Shutdown
1
Relay active
6
Heat or cool
11
Auto tune complete
12
Auto tune failed
13
Internal fault
14
Communications fault
15
Communications fault