4.4.
Alarm Status Page
Figure 11 shows a typical alarm page for JUNIOR. It displays the current status of the alarms for up to four
temperature sensors and three fans
3
. When an alarm is active the text indicates the condition, and is highlighted in
red. The latched alarms for shutdown and fault are indicated separately. A latched fault indicates an internal fault
has occurred and the unit should be power cycled to clear it.
The alarms are updated once every second and clear automatically when the alarm condition clears except the
shutdown or fault which have to be cleared either by switching the control mode to off or power cycling the unit.
Figure 11 Example JUNIOR Alarm status page
Alarm Status
3
Alarms are only valid for the sensors or fans that are connected and enabled.
Alarm Type
Alarm Status Description / Cause
Lat
ch
e
d
A
lar
m
s
Shutdown
Active
At least one alarm with shutdown option selected has tripped or Internal fault
has occurred.
Fault
Active
Indicates an internal fault has occurred.
T
e
m
p
e
rat
u
re
S
e
n
so
rs
Sensor A
Sensor B
Sensor C
Sensor D
Low
The measured temperature value has fallen below the Low Temp limit value.
High
The measured temperature value has risen above the High Temp limit value.
Fault
The sensor is short circuit, open circuit or not connected.
F
an
s
Speed
Low
The fan speed has fallen below the Speed Low limit.
High
The fan speed has gone above the Speed High limit.
Current
Fault
The average bridge current exceeds the Current High limit value.
Voltage
Fault
The maximum bridge voltage exceeds the Voltage High limit value.
Latched Alarms
Temperature Alarm
Fan Alarms