1  Important Safety Instruction 

 

1.1. 

An Important Notice 

1.1.1 For parallel system installation, please refer to parallel installation guide. 
1.1.2 Because of “LITTLE LEAKAGE CURRENTS” generated by EMI Filter of 

the UPS, it is necessary to double ensure if the earth of the UPS    is properly 
grounded before AC mains is connected with. 

1.1.3 To ensure safety in all applications where a UPS is hard wired to the 

Electrical Supply, ensure that the system is installed by a Qualified Electrical 
Contractor. 

1.1.4 The UPS has its own internal energy source (battery). Should the battery 

be switched on when no AC power is available, there could be voltage at the 
output terminals.   

1.1.5 Make sure that the AC Utility outlet is correctly grounded. 
1.1.6 Do not open the case, as there are no serviceable parts inside. Your 

Warranty will be void. 

1.1.7 Do not try to repair the unit yourself; contact your local supplier or your 

warranty will be void. 

1.1.8 Please make sure that the input voltage of the UPS matches the supply 

voltage. 

1.1.9 Use a certified input power cable with the correct plugs and sockets for 

the appropriate voltage system. 

1.1.10 To eliminate any overheating of the UPS, keep all ventilation openings 

free from obstruction, and do not store "things" on top of the UPS. Keep the 
UPS 30 cm away from the wall. 

1.1.11 Make sure the UPS is installed within the proper environment as 

specified. (0-40

  and 30-90% non-condensing humidity) 

1.1.12 Do not install the UPS in direct sunlight.    Your warranty may be void if 

the batteries fail. 

1.1.13 Install the UPS indoors as it is not designed for installation outdoors. 
1.1.14 Dusty, corrosive and salty environments can do damage to any UPS. 
1.1.15 Install the UPS away from objects that give off excessive heat and areas 

that are excessively wet. 

1.1.16 If liquids are split onto the UPS or foreign objects dropped into the unit, 

the warranty will be null and void. 

1.1.17 The battery will discharge naturally if the system is unused for any 

length of time. 

1.1.18 It should be recharged every 2-3 months if unused. If this is not done, 

then the warranty will be null and void. When installed and being used, the 
batteries will be automatically recharged and kept in top condition. 

1.1.19 This UPS supports electronic equipment in offices, telecommunications, 

process control, medical and security applications. Non-authorized technician 
is not allowed to install the UPS in the following areas. 

 

3

 

a. Medical equipment directly related to human life 
b. Elevator, Metro (Subway) system or any other equipment related to 

human safety. 

c. Public system or critical computer systems. 
 

1.1.20 Do not install the UPS in an environment with sparks, smoke or gas. 
1.1.21 Make sure the UPS is completely turned off when moving the UPS from 

one place to another. It might cause electrical shock if the output is not cut 
completely. 

1.1.22 The UPS offers CVCF (Constant Voltage Constant Frequency) setting 

function. To set RT series to be a CVCF shall be required by a qualified 
technician. 

a. For correct setting and wiring, please contact with your local agent. 
b. Do not do it by yourself; otherwise, your warranty will be void. 

 

1.1.23 This UPS has been designed and constructed to protect your assets 

from the wide range of power aberrations experienced on Utility power lines 
today. It is your insurance for reliable, clean and stable voltage supply. It is 
worth taking care to install the system correctly and to have it maintained 
correctly by your local dealer. 

1.1.24 SAVE THESE INSTRUCTIONS - This Manual Contains Important 

Instructions that should be followed during Installation and Maintenance of 
the UPS and Batteries. 

1.1.25 Intended for Installation in a Controlled Environment. 
1.1.26 CAUTION - A disconnect switch shall be provided by others for ac 

output circuit. To reduce the risk of fire, connect only to a circuit provided with 
branch circuit overcurrent protection for 30 amperes rating in accordance 
with the National Electric Code, ANSI/NFPA 70. 

1.1.27 CAUTION - To reduce the risk of fire, unit input connect only to a circuit 

provided with branch circuit overcurrent protection for 40 amperes rating in 
accordance with the National Electric Code, ANSI/NFPA 70. 

1.1.28 Use No. 10 AWG, 60

°

C copper wire and 22.1 lb-in Torque force when 

connecting to terminal block. 

 

1.2. 

Storage Instruction 

 

For extended storage through moderate climate, the batteries should be 

charged for 12 hours every 3 months by plugging the UPS power cord into the wall 
receptacle and turn on input breaker on front panel. Repeat this procedure every 2 
months under high temperature environment. 

Summary of Contents for 1_1 online mp series

Page 1: ...cation Port Explanation 11 3 Installation and Operation 12 3 1 Unpacking 12 3 2 Selecting Installation Position 13 3 3 Installation of Accessories Kit 14 3 4 Terminal Block Explanation 15 3 5 Operatio...

Page 2: ...ept in top condition 1 1 19 This UPS supports electronic equipment in offices telecommunications process control medical and security applications Non authorized technician is not allowed to install t...

Page 3: ...te control and monitoring easily 2 1 8Maintenance free sealed type battery minimizes after sales service 2 1 9Providing four different working modes such as Normal ECO CF50 and CF60 it may widely be u...

Page 4: ...verloading 31 Er14 Fan Error 32 Er15 Wrong Procedure to Enter Maintenance Mode 33 Er16 Output Parameters Set Error in Parallel System 34 Er17 ID Numbers are in conflict in Parallel System or ID number...

Page 5: ...us page or change the setting of the UPS To reconfirm the change of UPS Setting 9 2 3 2Rear Panel Explanation 5 6k PM 10K PM CB 1 Utility Input Breaker L12 N1 G1 L21 N22 G2 OUTPUT INPUT ON OF F S1 Ext...

Page 6: ...SNMP card you may combine them according to your demand However the R2E card RSE card and USE card are prohibited to be used simultaneously The bundled software of the UPS is compatible with many ope...

Page 7: ...s Wire No 7 is to be used at the input output terminal block of the UPS Please refer to Chapter 3 4 for installation A1 A2 A3 S1 S2 S3 S4 B1 B2 B3 x8 x6 x4 x2 x2 x2 x2 x1 x4 x4 for 2U for 3U PM10K onl...

Page 8: ...l Block Explanation L11 L12 N1 G1 L21 L23 N21 L22 N22 G2 OUTPUT INPUT BYPASS INPUT UTILITY INPUT L11 N1 BYPASS INPUT L12 N1 UTILITY INPUT G1 INPUT EARTH GROUND N22 L22 N21 L23 L21 UPS OUTPUT G2 OUTPUT...

Page 9: ...t Ground Use Mounting Cable Tie to fix cables Please refer to the specs of input current output current and recommended conductors listed as below a AC input and output b Battery input Model Maximum C...

Page 10: ...nputs are normal and the LCD display with parallel function will illustrate from drawing A1 drawing A2 to drawing B Otherwise the LCD display will illustrate from drawing A2 to drawing B A1 A2 B 19 3...

Page 11: ...ing G to drawing H then the UPS will be in self test Mode The UPS may offer energy to the output in a minute and the LCD display illustrates as drawing I In case of failure in pushing the UPS On Switc...

Page 12: ...pad to change the LCD display screen to drawing Q1 Q1 It shows buzzer On Q2 It shows buzzer Off 3 5 4 2 Press key pad to scroll down the screen and check the UPS settings The LCD display will show in...

Page 13: ...S2 It shows bypass voltage is adjusted to wider one T It shows Frequency Window is 3Hz 25 U It shows inverter output voltage V1 It shows the UPS is operated in normal mode V2 It shows the UPS is opera...

Page 14: ...ng T means the bypass frequency window of the Inverter Output the acceptable setting values are 3Hz and 1Hz 3 5 5 6 Drawing U means the acceptable Inverter Output Voltage of which voltage is 200Vac 20...

Page 15: ...e wirings of input and output correct b If the input voltage of the Utility is within the input window of the UPS In case problems or symptoms still exist please proceed the followings for proper adju...

Page 16: ...5 6 to trouble shoot the problem otherwise consult your local distributor for help 31 5 Bundled Software Installation Guide 5 1 Hardware Installation 1 Connect the male connector of RS232 cable to th...

Page 17: ...rmal Normal open contact Pin 4 Inverter On Pin 5 Battery Low Pin 6 Battery Bad or Abnormal Pin 7 UPS Alarm Pin 8 Common Pin 9 Shutdown UPS positive signal Pin 10 Shutdown UPS positive signal 6 4 2The...

Page 18: ...tage 240Vdc Recharge Time 4 hours to 90 5 hours to 80 DISPLAY Status On LED LCD Line Mode Backup Mode ECO Mode Bypass Supply Battery Low Battery Bad Disconnect Overload Transferring with interruption...