16. AC Control - Toshiba
Wiring Diagram
Commissioning Notes
Advanced Installation
Ÿ
Wire Platinum Elite Zone Control System, Gateway and AC Indoor Unit as shown ensuring
all wires are securely connected. Unless otherwise specified, leave DIP switches in their
default position.
Ÿ
Initialise the AC Unit with the Toshiba Wall Controller connected.
Ÿ
Ÿ
Ÿ
If the AC Indoor Unit is an RAV or VRF type, modify the SW1.1 and SW1.2 switches as
shown by the Indoor Unit Setting on the Wiring Diagram page.
Ensure the AC control temperature is set to be
measured from the AC return air sensor.
Ÿ
After commissioning, SW1.4 is left OFF. Gateway is in Slave mode.
Follow the Platinum Elite onscreen prompts to complete the AC setup.
The Platinum Elite system is capable of providing an external reference temperature to
compatible AC Units from either the temperature sensor in the Tablet or one of the
connected Temperature Sensors. Utilising this feature will potentially modify the control
loop for the AC Unit and as such requires precise configuration of the AC Unit, the Platinum
Elite Gateway and the Platinum Elite Tablet software to ensure the system functions
correctly.
For detailed information on Toshiba AC Unit system compatibility utilising external reference
temperatures and related Advanced Installation options, please visit the Platinum Elite Zone
Control System website www.platinumzoning.com or contact your ADA distributor.
The Wall Controller can
be wired in parallel with the Gateway.
NOTE: In some AC Indoor Unit models, the AB connector is not available. In it’s place there
is a pair of cables to connect the Wall Controller. Use these cables to make the AB
connection. Check the unit User Manual for more information.
AC Unit, Gateway and Platinum Elite Zone Control System can be powered up at the same
time, but if powered up separately, ensure AC Unit and Gateway are on before the
Platinum Elite Zone Control System.
Tablet
Cat6 cable
24VDC
Power
Supply
AC Indoor Unit PCB
Platinum Elite
Gateway
PEGT
SW1
SW3
SW4
SW1
Slave
Master
ON
ON
Gateway Master/Slave Setting
A+ B-
A B
A B
SW1
Not Defined
RAV
ON
ON
Indoor Unit Setting
VRF SMMS VRF SHRM
ON
ON
2-core cable (PETCW)
supplied with Platinum
Elite Cable Kit
2-core cable (PETCW)
supplied with Platinum
Elite Cable Kit
(AB connection has no
specific polarity)
Down/OFF
Up/ON
Wall Controller
A B
SW1
ON
Default Gateway Setting
Down/OFF
Up/ON