LC&D 800.345.4448
Pg. 7
“Analog” followed
by an integer (1,
2, 3) indicates this
is a PCC3 (3 Input
Photocell Card) .
Analog without an
integer is a PCC1
(single input) .
Refer to your
submittal document
for quantity and
location of photocells .
Time delay may be
1-30 minutes . Use the
TEST 5 SEC option
only when calibrating
the photocell .
Notice that the Off
set-point cannot
go above the On
set-point .
The Off set-point is
always higher than
the On set-point .
SENSOR ID#64-1
Analog 1: 0050
Time Delay: TEST 5 Sec
On when light level
falls below: 0000
Off when light level
rises above: 0001
SENSOR ID#64-1
Analog 1: 0050
Time Delay: TEST 5 Sec
On when light level
falls below: 0000
Off when light level
rises above: 0001
SENSOR ID#64-1
Analog 1: 0050
Time Delay: TEST 5 Sec
On when light level
falls below: 0030
Off when light level
rises above: 0031
SENSOR ID#64-1
Analog 1: 0050
Time Delay: TEST 5 Sec
On when light level
falls below: 0030
Off when light level
rises above: 0040
BASIC PHOTOCELL SETTINGS (cont’d)
To Program a Trigger Level:
Photocell Cards come with one or three
photocell inputs . Any of those photocells may
be used to control the Trigger .
1 . If “Analog 1” is displayed, SCROLL to select
the desired photocell .
2 . TAB to Time Delay .
3 . SCROLL to select Time Delay .
LC&D recommends a minimum delay of 10
minutes to prevent lights cycling on and off .
SCROLL to select the desired Time Delay .
4 . Tab to On Level .
5 . Scroll to desired ON level .
LC&D recommends “30” as a starting point
for roof-mounted photocells facing north .
Contact LC&D for assistance .
6 . Tab to Off Level .
7 . Scroll to desired OFF Level .
LC&D recommends “40” as a starting point
for roof-mounted photocells facing north .
8 . EXIT to Next Menu and refer to page 5 to
Program Loads .
Analog 1:
TEST 5 Sec
0030
0040
77