WHAT CONTROLS RELAYS
This menu is similar to the one above except that now what
controls a relay is listed.
Notice that now there are two fields that have to be scrolled,
first the panel or LCP number and then the load within that
panel.
WHAT CONTROLS GROUPS
Scroll to the Group number and then Hit ENTER. The Clock
will scan the bus and collect the data for display on the
screen.
WHATCONTROLS
GROUP 5
Hitentertoscan
theselectedgroup.
RELAY PROPERTIES Menu
This menu will change the parameters of each of the relays
on a relay card.
The address of the board is the number after the board.
Thus BOARD 1 is at address 1.
"NA" Refers to the fact that this board does not have a pro-
grammable delay time associated with it. The programma-
ble delay time is the number of 60 Hz cycles between each
relay operation. It may be set between 0 and 99 on GR
2416/32/48 series cards ONLY. A GR 2404 or GR 2408
does not have this capability. They have a preset delay of
two 60 Hz cycles.
Changing the Delay Time between Relay Operations on
a GR 2416 or GR 1416 Board.
To change the delay highlight the Board number that has a
"DLY" opposite it. Scroll UP or DOWN to change the delay
in 60ths of a second.
WHATCONTROLS
LCP1
LOAD -1
GROUP2
SWITCH ID#4B1
RLY PARAMs PAGE 1-1
BOARD 1
NA
BOARD 2 DLY 1
BOARD 3
NA
BOARD 4
NA
BOARD 5
NA
BOARD 6 DLY 1
RLY PARAMs PAGE 1-1
BOARD 1
NA
BOARD 2 DLY 1
BOARD 3
NA
BOARD 4
NA
BOARD 5
NA
BOARD 6
DLY 2
Page 38
WHATCONTROLS
GROUP 5
SCHEDULE5
SWITCHID#6Btn4
If one got the above result it would explain why the lights
were going off at the wrong times since any Group con-
trolled by a clock would not normally be controlled by a
switch.