Dry Contact to Energy Management System
Multiple inputs from an EMS system may be connected with
a single common as shown. Normally programmed as
MAINTAINED inputs.
IN2
IN1
+12V
+5V
Gnd
A powered Digilink has a 24 volt output to power most occupan-
cy sensors, 850 ma is available. Only use occupancy sensors
that have “dry contact outputs.” these are usually designated as
-RP or some other option to indicate that an additional relay has
been added for building automation purposes.
Connect occupancy sensors to the the Scene Input indicated on
the paperwork that came with the system.
A typical Occupancy sensor is a Mytech Light Owl sensor made
by Hubbell Building Automation. Here is their diagram:
Note that we do not need to connect 4 wires to this sensor since the Blue
White wire may be connected to the Ground or Black wire for the control
power.
Watt Stopper DT 200
BRN
RED
ORN
YEL
GRN
BLU
VIO
GRAY
Normally Closed Contact
Common
Normally Open Contact
Control Output 24Vdc
Common (Power)
Light Level Output (Slave)24Vdc
+24Vdc Power
Common For Slave Power
The Watt Stopper has very similar wiring to the Hub-
bell. The DT 200 has the auxiliary contacts built in
without being an option.
Novitas Sensors
Blue
Black
Red
Novitas is one of the few sensors on the market that
has an output that “pulls low” (using a transistor) and
can be used with the GR 2404-DIM without a separate
relay option.
Hooking up Occupancy Sensors to a Digilink
with Power.
NO (Normally Open)
-YELLOW/WHITE
COMMON-BLUE/WHITE
NC - BLACK/WHITE
POWER 24VDC
NO CONNECTION
NO CONNECTION
RED
BLACK
BLUE
GREY
Power
&
Control
Hubbell Building Automation LIGHTOWL
IN2
IN1
+12V
+5V
Gnd
Gnd
+24V
24 V
Gnd
Gnd
+5V
+12V
IN 1
IN 2
21