The name of the panel being edited will display on the top
line of the display as the number of the LCP field is scrolled.
When not changing the LCP number the name of the panel
and the name of the Group and its type are displayed alter-
nately each second.
Tabbing over to the Load number and Scrolling through the
relays for that panel will similarly bring up the names of the
relays as entered in the naming menu.
Each panel may have up to 48 loads in it. "Load" refers to
the relay number on a GR 2432 Card. Zone refers to the
center buttons which have been pre programmed with one
or more relays under its control.
A Group is edited by selecting the LCP number and then
the load or zone number to be operated on. Scrolling the
load number and hitting ENTER will either add or subtract
that load from the list of loads being operated on. If the load
is already listed then hitting ENTER will remove it from the
list. These loads are listed in smaller type below the editing
line.
GROUP 5
MNTN+TIMER
EDIT: LCP-1 LOAD-1
LCP1: 1-3
LCP1: 1-3
Name:LCP 1
MAINTAIN
EDIT
:
LCP-1
LOAD-1
Group Properties
The top right field in this screen is the Group Properties.
This describes what the group will do when initiated. A
Group may have the following properties :
a) MOMENTARY ON. This means that it will only turn ON
the Loads listed. Usually used with push button switches.
b) MOMENTARY OFF . This means that it will only turn
OFF loads listed. Usually used with push button switches.
c) MOMENTARY MIX. This means that loads can be turned
ON or OFF and mixed as the same event. Selecting a Load
and pressing ENTER on it once will make it an ON load, the
next press of ENTER will make it an OFF load and the next
press will remove it from the list.
The above three properties are usually used when the
Group is being operated on by a Switch rather than a
Schedule. The following three properties are usually the
ones used by a schedule.
d) MAINTAIN. Turns on the Group when the schedule turns
ON and OFF when it turns OFF.
e) MNTN-TIMER. This is Maintain with a timer. After the
clock turns off any override switch will bring on this zone for
a specified amount of time. Press ENTER on this field to
adjust the Timer period which defaults to 2 hours.
List of
Loads or
Zones
being
Operated.
GROUP 5 PARAMETERS
AUTOMATIC ON
TIMER OUT: 2:00:00 Hr
Page 31
37