MANUALCONTROL ON=
LCP-1 LOAD-
1
OFF=-
1- 3- 5- 7- 9- 11- 13- 15-
GROUP 5 PARAMETERS
AUTOMATIC ON
TIMER OUT: 2:00:00 Hr
BLINK WARNING: 05 min
f) MNTN+OFFSWEEP . This is similar to the Ma
Timer except that there is a Blink warning before the lights
go off. Press enter on the MNTN+OFFSWEEP field to set
the parameters of this field.
You may program the loads to come on at the ON time
(Automatic ON) or to not come on with the ON time (NO
AUTOMATIC ON.)
The application for NO AUTOMATIC ON is for energy sav-
ings in Offices which have low voltage override switches for
each office with personnel on staggered schedules. During
the night there is an OFF Sweep every (say) 2 hours. The
OFF Sweep is disabled by the Schedule at say 6am, then
as the occupants arrive they turn on their lights with their
local switches.
When to set the Blink Warning
The Blink warning starts at the time the schedule turns
OFF. Thus if the Blink warn time is 5 mins and the lights are
to go off at 6pm the schedule may be programmed to end
at 5.55pm.
Manual Override
The manual override Menu allows for manual operation of
remote loads. This feature is useful for remote operation
over a modem or computer hook up.
Select the load in the LCP that needs to be controlled and
press ENTER to toggle the status of the load.
Though the load will switch almost instantaneously the dis-
play may take as much as one second to update.
Setup Menu
The final selection on the USER MENU is the SET-UP
MENU.
We now get into some of the features of the system which
are less likely to be used by the end user.
Page 32
2- 4- 6- 8- 10- 12- 14- 16-
= Load is in Timer
Mode
= Load is in Timer
Mode and a BLINK
warning has been
issued
USER MENU
REVIEW SCHEDULE
MANUAL OVERRIDE
SETUP MENU
USER MENU
MANUAL CONTROL
REVIEW SCHEDULE
GROUP LOADS
PROGRAM SWITCH
iDIM/iDH SCENES
SETUP MENU
V 2.0 and earlier
Only here if an iDIM or iDH
are on the bus. These have
a separate Manual
38