Installation & Commissioning Guide - ESP Platinum ID Split Ducted Units
Doc. Part No. 0525-052
Rev. 4.0 180302
Page 8 of 16
UNIT LIFTING PROCEDURES
B. FORK LIFT METHOD
PROCEDURE:
1.
To move the unit around with a forklift, insert the fork tines
through the unit feet assembly, as shown in Fig. 2.
2.
Do not lift the unit through the electrical panel end of the unit
(See illustration for location of electrical panel end).
EQUIPMENT REQUIRED FOR CRANE LIFTING:
- 1 x shackle
- 2 x nylon slings
- 4 x rubber pads
NOTE:
Refer to catalogue for unit weight before selecting
shackles and slings.
PROCEDURE:
1. Slip nylon slings through the pallet as shown in Fig. 1.
2.
Use a Bow or Dee shackle to connect the slings.
3.
Ensure slings are protected by rubber pads or similar if slings
are draped across unit edges, corners, or air grilles . This will
prevent the unit from being damaged during lifting.
4.
Test lift the unit to determine exact unit balance and stability
before hoisting it to the installation location.
A. CRANE LIFTING METHOD
NOTE:
Crane lifting method is recommended for high rise lifting.
Fig. 1
Connect the loop ends of slings unto shackle
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
Detail - “
A
”
Slip nylon slings
through the pallet
Indoor
Unit
Pallet
PALLET FORK LIFTING HOLE DIMENSIONS
All dimensions in mm.
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
624
675
100
100
100
675
38
38
Fig. 2
ELECTRICAL
PANEL END
INSERT FORKLIFT
TINES HERE
INSERT FORKLIFT
TINES HERE
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
SRD175C / SRD175E
TECHNICAL & SELECTION DATA
UNIT FEATURES
Digital Scroll Compressor
•
10-100% Variable Refrigeration Capacity
•
Multiple Speed Outdoor Fans
•
Louvre Outdoor Coil Guard
•
Pre-charged with R410A Refrigerant
•
AM7-D8 Wall Controller Supplied as Standard
•
20 m of Data Cable Included
•
EXV (Electronic Expansion Valve)
•
Integral Fan Coil Safety Tray with Drain Kit
•
Indoor Coil Overheat Protection
•
Indoor Coil Anti-Freeze Protection
•
Smart Defrost Function
•
CONTROL FEATURES (AM7-D8)
7-Day Programmable Controller with 2 Events/Day
•
24- Hour ON/OFF Timer
•
Auto, Heat & Cool Modes
•
Auto/Continuous Indoor Fan Operation
•
3 Speed Indoor Fan Setting
•
Hot Start Feature
•
Home/Building Automation ON/OFF Capability
•
CONTROL OPTIONS
Remote Temperature Sensors
•
Zone Kit for Control up to 8 Zones
•
(See Integrated Zones, Barrels & Plenums Section)
Secondary Wall Controller with Mimic Logic
•
PLENUMS (Optional)
Supply Air Plenums are Available in a 2 way or 3 way
•
Con
fi guration (See Integrated Zones, Barrels and Plenums
Section for details of Spigots availability)
Return Air Plenums are Available with 2 x 400 mm Spigots
•
or
2 x 450 mm Spigots
SPECIFICATION SUMMARY
TOTAL *
NETT **
COOLING CAPACITY (kW) ***
18.12
17.40
SENSIBLE CAPACITY (kW) ***
14.81
14.09
HEATING CAPACITY (kW) ^
17.60
18.30
COOLING INPUT POWER (kW) ^^
6.07
HEATING INPUT POWER (kW) ^^
5.44
EER
2.99
2.87
COP
3.24
3.37
INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^
740 / 920 / 1100
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH
52.0 / 54.0
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
69.0 / 71.0
POWER SUPPLY - OUTDOOR
240 V / 1 Ph / 50 Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
22.0 / 3.1 / 25.1
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
32.6 / 4.0 / 36.6
CIRCUIT BREAKER AND CABLE AMPS
40.0
APPROXIMATE STARTING AMPS
<45.0
WEIGHT (kg) -- INDOOR / OUTDOOR
75.0 / 180.0
OUTDOOR UNIT MODEL
SRD175C
INDOOR UNIT MODEL
SRD175E
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 27
0
C DB / 19
0
C WB entering air temperatures and 35
0
C ambient.
At 20
0
C DB entering air temperature and 7
0
C DB / 6
0
C WB ambient.
Input power includes indoor fan kW.
Max. - Min. air
fl
ow application range.
Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.
See Speci
fi cations sheet for Cable Size and Circuit Breaker Size details.
Note: Use input power to estimate running cost.
*
**
***
^
^^
^^^
^^^^
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.
SRD175C-
0100
/ SRD175E-
0100
-P1- 090326
R
R410A
DIGITAL SCROLL
COMPRESSOR
ESP SPLIT DUCTED UNIT
“
A
”
WH&S regulations must be observed and will
take precedence during lifting process.
WARNING
Make sure rigging equipment, accessories and plant are
sufficiently and safely capable to lift the unit in order to
prevent potential damage to property, severe personal
injury or death. Please check unit weight and weight
distribution points on unit drawing dimensions section.
DANGER
DO NOT LIFT UNIT from this end in order to
prevent damage to electrical panel & pipes.
CAUTION
CAUTION
Length of fork lift tines must pass the unit
middle section, in order to safely carry the unit.