Installation & Commissioning Guide - ESP Platinum ID Split Ducted Units 

Doc. Part No. 0525-052  

Rev. 4.0 180302

Page 2 of  16

TABLE OF CONTENTS

INTRODUCTION

CONGRATULATIONS 

on your purchase of an Actron 

Air Platinum Series air conditioning unit ! This unit has 

been designed and engineered to provide optimum air 

conditioning and to achieve maximum energy efficiency. 

Your air conditioning system has been manufactured from 

the highest quality materials. Numerous “in house” and 

“external” inspection and test procedures were conducted 

to your air conditioning to ensure satisfactory operation.     

INFORMATION ABOUT THIS GUIDE

This guide provides installation instructions, specific 

to your split ducted indoor unit. Read this manual 

thoroughly and take into consideration all specifications 

and instructions to insure correct installation and safe 

operation of your air conditioning system. 

   

Keep this document near the unit for future 

reference. Ensure that all technicians that work 

on the unit can refer to this manual at any time.

PRODUCT INSPECTIONS

Fully check your air conditioning unit and all items 

against the bill of loading upon receiving your shipment. 

Inspect the unit, components and accessories for any 

sign of shipping damage. If there is any damage to the 

unit, contact Actron Air Customer Care Department 

immediately on: 

1800 522 722.

Check the unit nameplate to verify the model, serial 

number, electrical rated specifications and details are 

correct.

CODES, REGULATIONS AND STANDARDS

The installer and/or contractor assumes responsibility 

to ensure that unit installation complies with the 

relevant council, state / federal codes, regulations and 

building code standards. All electrical wiring must be in 

accordance with current electrical authority regulations 

and all wiring connections to be as per electrical diagram 

provided with the unit.

SAFETY INSTRUCTIONS

1.  Only licensed HVAC technicians

*

 should install and 

service this air conditioning equipment. Improper 

service or alteration by unqualified technician could 

result in significant and major damage to the product 

or property which may render your warranty null 

and void. Such unqualified service could also lead 

to severe physical injury or death. Follow all safety 

instructions in this literature and all warning labels 

that are attached to the equipment.

2.  Prevailing WH&S regulations must be observed 

and will take precedence to the safety instructions 

contained on this manual. Safe work practices and 

environment must be the paramount importance in 

the performance of all the service procedures.

3.  Ensure that unit installation complies with relevant 

council regulations and building code standards.

4.  All electrical wiring must be in accordance with 

current electrical authority regulations and all wiring 

connections to be as per electrical diagram provided.

5. 

Secure the fans against accidental contact. Beware 

of pinch point and sharp edges which can cause 

cutting injury.

6.  Always wear appropriate PPE, remove any dangling 

jewellery and protect long hair by wearing a cap.

7. 

Make sure that safety guards and panel covers are 

always firmly secured and not damaged.

8. 

This appliance is not intended for use by young 

children or infirm persons unless they have been 

adequately supervised by a responsible person to 

ensure that they can use the appliance safely. Young 

children should be supervised to ensure that they do 

not play with the appliance.

9. 

Installer must incorporate a means of electrical 

disconnection (isolator) in the sub mains fixed 

wiring in accordance with the Australian wiring rule 

(AS3000).

10. Secure the power cords and control cables that goes 

in/out the unit. Use the cable ties provided in the 

control box.

 *

 

Qualifications required will be appropriate Electrical, 

Refrigeration and Refrigerant Handling License & Training, 

dependent on local State/Territory regulations.

This indoor unit is designed to match only with ActronAir 

outdoor unit as specified in the Technical Selection 

Catalogue. 

This unit is designed for use with R410A refrigerant 

only.

The unit is supplied with factory charged dry air. Beware 

of the pressurised air charge when purging. Remove 

the caps from the connection points and purge the 

system only when the field pipes connection are ready 

to be completed.  

IMPORTANT NOTES TO THE INSTALLER

Introduction ....................................................................

Safety Instructions..........................................................

Components Overview...................................................

Unit Dimensions and Clearances ..................................

Two-Piece Fan Coil .......................................................
Installation Instructions .................................................

Unit Lifting Procedures ..................................................
Condensate & Safety Tray Drainage Instructions .........
Zone Barrels Mounting Instructions ..............................

Wiring Diagram..............................................................
Maximum Cable Lengths...............................................
Maintenance Frequency Checklist ................................
Key Parts List ................................................................

2
2
3
4
6
7
8
9

10

11

12
14
15

Summary of Contents for ESP PLATINUM ERQ2-14AS

Page 1: ... and or reproduction are prohibited without written consent from Actron Air Please Read This Guide Congratulations on your purchase of an Actron Air air conditioning unit This unit has been designed and manufactured with the highest quality standard in mind Please read this guide thoroughly and keep it near the unit for future reference INDOOR UNITS ESP PLATINUM ERQ2 14AS ERQ3 17AS ERQ4 19AS ESP P...

Page 2: ...ety instructions in this literature and all warning labels that are attached to the equipment 2 Prevailing WH S regulations must be observed and will take precedence to the safety instructions contained on this manual Safe work practices and environment must be the paramount importance in the performance of all the service procedures 3 Ensure that unit installation complies with relevant council r...

Page 3: ...o change without notice Copyright 2017 Actron Engineering Pty Ltd Page 3 of 16 COMPONENTS OVERVIEW INDOOR UNIT COMPONENTS OVERVIEW Indoor Unit EC Motor ID Fans ID Coil 8Z VAQ Module Lid Control Panel Indoor Control Panel SRD175C SRD175E DATA DIGITAL SCROLL COMPRESSOR DUCTED UNIT Indoor Unit Control Board EMC Filter ...

Page 4: ...d the outside perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION STACKING OF UNITS ONE IN FRONT OF THE OTHER DISTANCE BET A B SIDE BY SIDE DISTANCE BET A C DUCT WORK 800 mm HEIGHT CLEARANCE 340 B D C A DUCT WORK DUCT WORK 800 mm SERVICE CLEARAN...

Page 5: ...units or between the unit and the outside perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION OVERALL NOMINAL DIMENSION H x W x D 435 x 1420 x 680 SUPPLY DUCT H x W 300 x 715 RETURN DUCT 360 x 1140 DRAIN CONNECTION 20mm OD TOP VIEW FRONT VIEW SI...

Page 6: ...Y PLENUM 2 WAY SUPPLY PLENUM TWIN SPIGOT DUCT PLATE 1 WAY SUPPLY PLENUM UNIT FEATURES flexible ducting Ducting is attached to each section by either a 1 2 or 3 way EASY FIT supply plenum or a twin spigot duct plate these can be fitted to either side of each section ADD ON COOLING is simply achieved by fitting only the coil section into an existing ventilation system Note External static pressure i...

Page 7: ...nt for a clean hygienic room condition Air filters must be placed in an easily accessible location for service and maintenance NOTES 1 Air filters are not supplied with the unit as individual air filtration requirements are varied 2 Ensure that filters are cleaned replaced regularly SUPPLY AIR RETURN AIR DUCT OPTIONAL Supply Air plenums and Duct Plates twin spigot are available in order to facilit...

Page 8: ...riable Refrigeration Capacity Multiple Speed Outdoor Fans SPECIFICATION SUMMARY OUTDOOR UNIT MODEL SRD INDOOR UNIT MODEL SRD R410A DIGITAL SCROLL COMPRESSOR ESP SPLIT DUCTED UNIT 624 675 100 100 100 675 38 38 Fig 2 ELECTRICAL PANEL END INSERT FORKLIFT TINES HERE INSERT FORKLIFT TINES HERE SRD175C SRD175E ELECTION DATA DIGITAL SCROLL SPLIT DUCTED UNIT SRD175C SRD175E ECTION DATA SPECIFICATION SUMMA...

Page 9: ... TRAY DOES NOT OVERFLOW INDOOR COIL RETURN AIR INDOOR COIL CONDENSATE DRAIN MUST BE RUN SEPERATLY FROM THE SAFETY TRAY DRAIN SAFETY TRAY DRAIN CONNECTION CONDENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION INSTALL A T PI...

Page 10: ...ONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL BARRELS MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS Duct Duct Zone Barrel Damper Motor on Top of the Zone Barrel TYPE 10 250 mm PART NUMBER ZB 10 250 IN...

Page 11: ...REEN WIRE REMOVED ON INDOOR UNIT SCREEN FOIL CLAMPED TO P CLIP ON OUTDOOR UNIT POWER DATA YELLOW CAT5E CABLE POWER ONLY YELLOW CAT5E CABLE MASTER SECONDARY OPTIONAL WiFi WiFi RF RF MODULATION ZONING QUEIB DATA ZONE 8 ZONE 7 ZONE 6 ZONE 5 ZONE 4 ZONE 3 ZONE 2 ZONE 1 TO ZONE 2 8 240V MAINS ZONE MOTOR ZONE CONTROL 1 REMOTE SENSOR 1 LOG RJ45 SOCKETS FOR ACTRON AIR CAT5E SPEC CABLES ONLY REFER TO QUE C...

Page 12: ...lip OUTDOOR UNIT TO OUTDOOR PCB MODEL R 410A CAUTION PLEASE THERE IS NO GAS PRESSURE IN THE FAN COIL UNIT BEFORE REMOVING COPPER END CAPS ENSURE 3670 043 Sensor 4 CAUTION LIVE ELECTRICAL WIRING AUTHORISED TECHNICIANS ONLY INTERNAL CONTROL ISOLATOR FITTED MODEL MEPS CERTIFIED A U S TRALIAN M A D E A U STRALIAN OW N E D R 410A 1 DIAGRAM SHOWING SCREEN FOIL CLAMPING Metal P Clip Electrical Panel 2 CO...

Page 13: ...MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS MOUNTING SCREWS ITEM PART NUMBER 7 METER CABLE 4070 004 ZONE MOTOR ONLY TRANSFORMER ONLY ZM 24V 2045 046 20 METER CABLE 4070 007 2 WAY RJ45 JOINER 2045 121 3 WAY RJ45 JOINER 4070 008 ZONE OPTION 2 1 5V AAA 1 5V AAA 1 5V AAA 1 5V ...

Page 14: ...ng Panels and Frames Visual check for damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as necessary to negate possibility ...

Page 15: ...ESCRIPTION PART NUMBER QUANTITY QUANTITY QUANTITY 1 EC ID Fan 2520 333 1 1 2 EC ID Fan 2520 334 1 3 Indoor Coil Assembly 1040 156 1 4 Indoor Coil Assembly 1040 254 1 5 Indoor Coil Assembly 1040 177 1 6 Coil Piston 4540 088 1 7 Coil Piston 4540 098 1 8 Coil Piston 4540 128 1 9 ID Control Board AFS QUEIB1 1 2020 154 1 1 1 10 Zone Module 8Z VAQ 1 1 1 11 Filter Board 4080 013 1 1 1 12 Yellow Cat5e Cab...

Page 16: ...Ltd ABN 34 002 767 240 HEAD OFFICE SYDNEY AUSTRALIA Printed in Australia Part No 0525 052 Rev No 4 0 180302 1800 119 229 actronair com au Copyright 2017 Actron Engineering Pty Ltd Refrigerant Trading Authorisation No AU06394 ...

Reviews: