ActronAir

 

is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.

Copyright © 2017 Actron Engineering Pty. Ltd.

Page 3 of  16

COMPONENTS OVERVIEW

INDOOR UNIT COMPONENTS OVERVIEW

Indoor

Unit

EC Motor

ID Fans

ID Coil

8Z-VAQ Module

Lid - Control Panel

Indoor 

Control Panel

SRD175C / SRD175E

 TECHNICAL & SELECTION DATA

UNIT FEATURES

Digital Scroll Compressor

10-100% Variable Refrigeration Capacity

Multiple Speed Outdoor Fans

Louvre Outdoor Coil Guard

Pre-charged with R410A Refrigerant

AM7-D8 Wall Controller Supplied as Standard

20 m of Data Cable Included

EXV (Electronic Expansion Valve)

Integral Fan Coil Safety Tray with Drain Kit 

Indoor Coil Overheat Protection

Indoor Coil Anti-Freeze Protection

Smart Defrost Function

CONTROL FEATURES (AM7-D8)

7-Day Programmable Controller with 2 Events/Day 

24- Hour ON/OFF Timer

Auto, Heat & Cool Modes

Auto/Continuous Indoor Fan Operation

3 Speed Indoor Fan Setting

Hot Start Feature

Home/Building Automation ON/OFF Capability

CONTROL OPTIONS

Remote Temperature Sensors

Zone Kit for Control up to 8 Zones 

    (See Integrated Zones, Barrels & Plenums Section)

Secondary Wall Controller with Mimic Logic

PLENUMS (Optional)

Supply Air Plenums are Available in a 2 way or 3 way

    Con

fi guration (See Integrated Zones, Barrels and Plenums

    Section for details of Spigots availability)

Return Air Plenums are Available with 2 x 400 mm Spigots 

or                    

2 x 450 mm Spigots

SPECIFICATION SUMMARY

TOTAL *

NETT **

COOLING CAPACITY (kW) *** 

18.12

17.40

SENSIBLE CAPACITY (kW) ***

14.81

14.09

HEATING CAPACITY (kW) ^

17.60

18.30

COOLING INPUT POWER (kW) ^^

6.07

HEATING INPUT POWER (kW) ^^

5.44

EER

2.99

2.87

COP

3.24

3.37

INDOOR AIRFLOW (l/s) -- MIN. / NOMINAL / MAX. ^^^

740 / 920 / 1100

OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) -- LOW / HIGH

52.0 / 54.0

OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH

69.0 / 71.0

POWER SUPPLY - OUTDOOR 

 240 V / 1 Ph / 50 Hz

POWER SUPPLY - INDOOR

240V / 1 Ph / 50 Hz

RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **

22.0 / 3.1 / 25.1

FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^

32.6 / 4.0 / 36.6

CIRCUIT BREAKER AND CABLE AMPS 

40.0

APPROXIMATE STARTING AMPS

<45.0

WEIGHT (kg) -- INDOOR / OUTDOOR

75.0 / 180.0

OUTDOOR UNIT MODEL

SRD175C

INDOOR UNIT MODEL

SRD175E

Based on unit rating excluding indoor fan kW.

Measured and tested in accordance with AS/NZS 3823.1.2.

At 27

0

C DB / 19

0

C WB entering air temperatures and 35

0

C ambient.

At 20

0

C DB entering air temperature and 7

0

C DB / 6

0

C WB ambient.

Input power includes indoor fan kW.

Max. - Min. air

fl

 ow application range.

Full Load Amps are based on Compressor and Fan Motors’ maximum expected current.

See Speci

fi cations sheet for Cable Size and Circuit Breaker Size details.

Note: Use input power to estimate running cost.

*

**

***

^

^^

^^^

^^^^

ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifi cations are subject to change without notice, Please check prior to purchase.

SRD175C-

0100

 / SRD175E-

0100

 -P1- 090326

R

R410A

DIGITAL SCROLL

COMPRESSOR

ESP SPLIT DUCTED UNIT

Indoor Unit

Control Board

EMC Filter

Summary of Contents for ESP PLATINUM ERQ2-14AS

Page 1: ... and or reproduction are prohibited without written consent from Actron Air Please Read This Guide Congratulations on your purchase of an Actron Air air conditioning unit This unit has been designed and manufactured with the highest quality standard in mind Please read this guide thoroughly and keep it near the unit for future reference INDOOR UNITS ESP PLATINUM ERQ2 14AS ERQ3 17AS ERQ4 19AS ESP P...

Page 2: ...ety instructions in this literature and all warning labels that are attached to the equipment 2 Prevailing WH S regulations must be observed and will take precedence to the safety instructions contained on this manual Safe work practices and environment must be the paramount importance in the performance of all the service procedures 3 Ensure that unit installation complies with relevant council r...

Page 3: ...o change without notice Copyright 2017 Actron Engineering Pty Ltd Page 3 of 16 COMPONENTS OVERVIEW INDOOR UNIT COMPONENTS OVERVIEW Indoor Unit EC Motor ID Fans ID Coil 8Z VAQ Module Lid Control Panel Indoor Control Panel SRD175C SRD175E DATA DIGITAL SCROLL COMPRESSOR DUCTED UNIT Indoor Unit Control Board EMC Filter ...

Page 4: ...d the outside perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION STACKING OF UNITS ONE IN FRONT OF THE OTHER DISTANCE BET A B SIDE BY SIDE DISTANCE BET A C DUCT WORK 800 mm HEIGHT CLEARANCE 340 B D C A DUCT WORK DUCT WORK 800 mm SERVICE CLEARAN...

Page 5: ...units or between the unit and the outside perimeter is available 4 Minimum service access clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access THIRD ANGLE PROJECTION OVERALL NOMINAL DIMENSION H x W x D 435 x 1420 x 680 SUPPLY DUCT H x W 300 x 715 RETURN DUCT 360 x 1140 DRAIN CONNECTION 20mm OD TOP VIEW FRONT VIEW SI...

Page 6: ...Y PLENUM 2 WAY SUPPLY PLENUM TWIN SPIGOT DUCT PLATE 1 WAY SUPPLY PLENUM UNIT FEATURES flexible ducting Ducting is attached to each section by either a 1 2 or 3 way EASY FIT supply plenum or a twin spigot duct plate these can be fitted to either side of each section ADD ON COOLING is simply achieved by fitting only the coil section into an existing ventilation system Note External static pressure i...

Page 7: ...nt for a clean hygienic room condition Air filters must be placed in an easily accessible location for service and maintenance NOTES 1 Air filters are not supplied with the unit as individual air filtration requirements are varied 2 Ensure that filters are cleaned replaced regularly SUPPLY AIR RETURN AIR DUCT OPTIONAL Supply Air plenums and Duct Plates twin spigot are available in order to facilit...

Page 8: ...riable Refrigeration Capacity Multiple Speed Outdoor Fans SPECIFICATION SUMMARY OUTDOOR UNIT MODEL SRD INDOOR UNIT MODEL SRD R410A DIGITAL SCROLL COMPRESSOR ESP SPLIT DUCTED UNIT 624 675 100 100 100 675 38 38 Fig 2 ELECTRICAL PANEL END INSERT FORKLIFT TINES HERE INSERT FORKLIFT TINES HERE SRD175C SRD175E ELECTION DATA DIGITAL SCROLL SPLIT DUCTED UNIT SRD175C SRD175E ECTION DATA SPECIFICATION SUMMA...

Page 9: ... TRAY DOES NOT OVERFLOW INDOOR COIL RETURN AIR INDOOR COIL CONDENSATE DRAIN MUST BE RUN SEPERATLY FROM THE SAFETY TRAY DRAIN SAFETY TRAY DRAIN CONNECTION CONDENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION INSTALL A T PI...

Page 10: ...ONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL BARRELS MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS Duct Duct Zone Barrel Damper Motor on Top of the Zone Barrel TYPE 10 250 mm PART NUMBER ZB 10 250 IN...

Page 11: ...REEN WIRE REMOVED ON INDOOR UNIT SCREEN FOIL CLAMPED TO P CLIP ON OUTDOOR UNIT POWER DATA YELLOW CAT5E CABLE POWER ONLY YELLOW CAT5E CABLE MASTER SECONDARY OPTIONAL WiFi WiFi RF RF MODULATION ZONING QUEIB DATA ZONE 8 ZONE 7 ZONE 6 ZONE 5 ZONE 4 ZONE 3 ZONE 2 ZONE 1 TO ZONE 2 8 240V MAINS ZONE MOTOR ZONE CONTROL 1 REMOTE SENSOR 1 LOG RJ45 SOCKETS FOR ACTRON AIR CAT5E SPEC CABLES ONLY REFER TO QUE C...

Page 12: ...lip OUTDOOR UNIT TO OUTDOOR PCB MODEL R 410A CAUTION PLEASE THERE IS NO GAS PRESSURE IN THE FAN COIL UNIT BEFORE REMOVING COPPER END CAPS ENSURE 3670 043 Sensor 4 CAUTION LIVE ELECTRICAL WIRING AUTHORISED TECHNICIANS ONLY INTERNAL CONTROL ISOLATOR FITTED MODEL MEPS CERTIFIED A U S TRALIAN M A D E A U STRALIAN OW N E D R 410A 1 DIAGRAM SHOWING SCREEN FOIL CLAMPING Metal P Clip Electrical Panel 2 CO...

Page 13: ...MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS MOUNTING SCREWS ITEM PART NUMBER 7 METER CABLE 4070 004 ZONE MOTOR ONLY TRANSFORMER ONLY ZM 24V 2045 046 20 METER CABLE 4070 007 2 WAY RJ45 JOINER 2045 121 3 WAY RJ45 JOINER 4070 008 ZONE OPTION 2 1 5V AAA 1 5V AAA 1 5V AAA 1 5V ...

Page 14: ...ng Panels and Frames Visual check for damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as necessary to negate possibility ...

Page 15: ...ESCRIPTION PART NUMBER QUANTITY QUANTITY QUANTITY 1 EC ID Fan 2520 333 1 1 2 EC ID Fan 2520 334 1 3 Indoor Coil Assembly 1040 156 1 4 Indoor Coil Assembly 1040 254 1 5 Indoor Coil Assembly 1040 177 1 6 Coil Piston 4540 088 1 7 Coil Piston 4540 098 1 8 Coil Piston 4540 128 1 9 ID Control Board AFS QUEIB1 1 2020 154 1 1 1 10 Zone Module 8Z VAQ 1 1 1 11 Filter Board 4080 013 1 1 1 12 Yellow Cat5e Cab...

Page 16: ...Ltd ABN 34 002 767 240 HEAD OFFICE SYDNEY AUSTRALIA Printed in Australia Part No 0525 052 Rev No 4 0 180302 1800 119 229 actronair com au Copyright 2017 Actron Engineering Pty Ltd Refrigerant Trading Authorisation No AU06394 ...