Maintenance, troubleshooting, spare parts and dismantling
ACT 600 – 5000
31 – EN
8 Maintenance,
troubleshooting,
spare parts and dismantling
8.1
Checks and maintenance
Only qualified personnel should perform troubleshooting and or
maintenance
operations.
Prior to performing any maintenance or service, be sure that :
no part of the machine is powered and that it cannot be connected to the mains
supply.
no part of the machine is under pressure and that it cannot be connected to the
compressed air system.
maintenance personnel have read and understand the safety and operation
instructions in this manual.
Before attempting any maintenance operation on the dryer, shut it down and wait at
least 30 minutes. components can reach high temperature during operation. Avoid
contact until system or component has dissipated heat.
Daily
Verify that the DewPoint displayed on the electronic instrument is correct.
Check the proper operation of the condensate drain systems.
Verify the condenser for cleanliness (Air-Cooled).
Every 200 hours or monthly
With an air jet (max. 2 bar / 30 psig) blowing from inside towards outside
clean the condenser; repeat this operation blowing in the opposite way; be
careful not to damage the aluminum fins of the cooling package (Air-Cooled)
Close the manual condensate drain valve, unscrew the strainer (if installed) and clean it with
compressed air and brush. Reinstall the strainer properly tight, and then open the manual valve.
At the end, check the operation of the machine
Every 1000 hours or yearly
Verify for tightness all the screws of the electric system and that all the “Disconnects-Tabs” type
connections are in their proper position inspect unit for broken, cracked or bare wires.
Inspect refrigerating circuit for signs of oil and refrigerant leakage.
Measure and record amperage. Verify that readings are within acceptable parameters as listed
in specification table.
Inspect flexible hoses, and replace if necessary.
At the end, check the operation of the machine.
Every 8000 hours
Replace Electronic drainer service unit
Summary of Contents for 1500-2500
Page 17: ...Technical data ACT 600 5000 17 EN 6 Technical data 6 1 Technical data ACT 600 5000 3 460 60 ...
Page 18: ...Technical data 18 EN ACT 600 5000 6 2 Technical data ACT 600 5000 3 575 60 ...
Page 38: ...Maintenance troubleshooting spare parts and dismantling 38 EN ACT 600 5000 ...
Page 41: ...Attachments ACT 600 5000 41 EN 9 1 Dryers dimensions 9 1 1 ACT 600 1250 ...
Page 42: ...Attachments 42 EN ACT 600 5000 9 1 2 ACT 1500 2500 ...
Page 43: ...Attachments ACT 600 5000 43 EN 9 1 3 ACT 3000 3750 ...
Page 44: ...Attachments 44 EN ACT 600 5000 9 1 4 ACT 4000 5000 ...
Page 45: ...Attachments ACT 600 5000 45 EN 9 2 Exploded views 9 2 1 ACT 600 1250 Air Cooled ...
Page 46: ...Attachments 46 EN ACT 600 5000 9 2 2 ACT 600 1250 Water Cooled ...
Page 47: ...Attachments ACT 600 5000 47 EN 9 2 3 ACT 1500 2500 Air Cooled ...
Page 48: ...Attachments 48 EN ACT 600 5000 9 2 4 ACT 1500 2500 Water Cooled ...
Page 49: ...Attachments ACT 600 5000 49 EN 9 2 5 ACT 3000 3750 Air Cooled ...
Page 50: ...Attachments 50 EN ACT 600 5000 9 2 6 ACT 3000 3750 Water Cooled ...
Page 51: ...Attachments ACT 600 5000 51 EN 9 2 7 ACT 4000 5000 Air Cooled ...
Page 52: ...Attachments 52 EN ACT 600 5000 9 2 8 ACT 4000 5000 Water Cooled ...
Page 66: ...Blank pages 66 EN ACT 600 5000 10 Blank pages ...