Technical description
ACT 600 – 5000
29 – EN
7.15.10
How to change operating parameters – SETUP Menu
The setup menu can be used to change the dryer’s operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer
is not responsible for malfunctioning or failure due to modification to the operating
parameters.
With dryer ON or OFF and not in other menus, simultaneously press buttons
info
set
for at least 5 seconds
to enter the setup menu.
Access to the info menu is confirmed by message
on the display (first parameter of menu). Use
arrows
and
to move to following/previous one.
Keep
info
pressed to display the value of the selected parameter and use arrows
and
to change
the value. Release the button
info
to confirm the value and skip to following parameter.
Press
ESC
to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
ID Description Limits
Resolution
Standard
setup
Ton – drain time ON : time ON condensate drain valve
00 = Electronic drainer installed
00 … 20 sec
1 sec
00
ToF - drain time OFF : pause time for condensate
drain valve
1 … 20 min
1 min
1
HdA - High DewPoint Alarm : Alarm threshold for a
high DewPoint (the alarm disappears when the
temperature drop 1°C / 2°F below alarm point)
0.0…25.0 °C
or
32 … 77 °F
0.5 °C
or
1 °F
20
or
68
Hdd - High DewPoint Delay : high DewPoint alarm
enable delay
01 … 20
minutes
1 min
15
HdS - High DewPoint alarm STOP : select if high
DewPoint alarm stops dryer (YES) or does not stop
dryer (nO)
YES … nO
-
nO
SrV - Service Setting: setting of service warning timer.
00 = service warning timer disabled.
0.0 … 9.0
(x 1000)
hours
0.5
(x1000)
hours
8.0
SCL - Scale: display scale of temperatures and
pressure.
(Note : setting °C = temperature in °C and pressure in bar;
setting °F = temperature in °F and pressure in psi)
°C … °F
-
°F
AS - Auto Restart : automatic re-start at power supply.
YES = at power supply dryer starts up again
automatically (if it was ON)
nO = at power supply dryer is always OFF
YES … nO
-
nO
Ard - Auto Reset service drain : automatic reset of
service drain
YES = automatic reset at normal conditions
nO = manual reset required
YES … nO
-
YES
IPA - IP Address : selection of IP address to use in
serial connection line
1 … 255
1
1
AS = YES - CAUTION -
THE DRYER MAY POWER UP WITHOUT BEING ACTED UPON.
THE USER WILL BE RESPONSIBLE FOR THE INSTALLATION OF PROPER PROTECTIONS
FOR POSSIBLE SUDDEN POWER RESTORATION TO THE DRYER.
Summary of Contents for 1500-2500
Page 17: ...Technical data ACT 600 5000 17 EN 6 Technical data 6 1 Technical data ACT 600 5000 3 460 60 ...
Page 18: ...Technical data 18 EN ACT 600 5000 6 2 Technical data ACT 600 5000 3 575 60 ...
Page 38: ...Maintenance troubleshooting spare parts and dismantling 38 EN ACT 600 5000 ...
Page 41: ...Attachments ACT 600 5000 41 EN 9 1 Dryers dimensions 9 1 1 ACT 600 1250 ...
Page 42: ...Attachments 42 EN ACT 600 5000 9 1 2 ACT 1500 2500 ...
Page 43: ...Attachments ACT 600 5000 43 EN 9 1 3 ACT 3000 3750 ...
Page 44: ...Attachments 44 EN ACT 600 5000 9 1 4 ACT 4000 5000 ...
Page 45: ...Attachments ACT 600 5000 45 EN 9 2 Exploded views 9 2 1 ACT 600 1250 Air Cooled ...
Page 46: ...Attachments 46 EN ACT 600 5000 9 2 2 ACT 600 1250 Water Cooled ...
Page 47: ...Attachments ACT 600 5000 47 EN 9 2 3 ACT 1500 2500 Air Cooled ...
Page 48: ...Attachments 48 EN ACT 600 5000 9 2 4 ACT 1500 2500 Water Cooled ...
Page 49: ...Attachments ACT 600 5000 49 EN 9 2 5 ACT 3000 3750 Air Cooled ...
Page 50: ...Attachments 50 EN ACT 600 5000 9 2 6 ACT 3000 3750 Water Cooled ...
Page 51: ...Attachments ACT 600 5000 51 EN 9 2 7 ACT 4000 5000 Air Cooled ...
Page 52: ...Attachments 52 EN ACT 600 5000 9 2 8 ACT 4000 5000 Water Cooled ...
Page 66: ...Blank pages 66 EN ACT 600 5000 10 Blank pages ...