Maintenance, troubleshooting, spare parts and dismantling
34 – EN
ACT 600 – 5000
SYMPTOM
POSSIBLE CAUSE - SUGGESTED ACTION
Compressor
discharge
temperature too
high.
Check which of the following has caused the failure :
1. Eccessive thermal load – restore nominal conditions.
2. The inlet air is too hot - restore nominal conditions.
3. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation (Air-Cooled).
4. The condenser unit is dirty - clean it (Air-Cooled).
5. The fan doesn’t work - see specific point (Air-Cooled).
6. The fan is always on – verify proper operation of fan power contactor (see
KV1/KV2 on electric diagram) and/or of pressure transducer (see BHP on electric
diagram) – (Air-Cooled).
7. The hot gas by-pass valve requires re-adjusting – contact a specialized technician
to restore nominal setting.
8. The temperature of the cooling water is too low – restore nominal conditions
(Water-Cooled).
9. The cooling water flow adjusting valve requires re-adjusting - contact a specialized
technician to restore nominal setting (Water-Cooled).
10.
Refrigerant gas leak - contact a refrigeration engineer.
Condensing
pressure too
high
Check which of the following has caused the failure :
1. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation (Air-Cooled).
2. The condenser unit is dirty - clean it (Air-Cooled).
3. The fan doesn’t work - see specific point (Air-Cooled).
4. The temperature of the cooling water is too hot – restore nominal conditions
(Water-Cooled).
5. Cooling water flow is not sufficient – restore nominal conditions (Water-Cooled).
Condensing
pressure too
low
Check which of the following has caused the failure :
1. The fan is always on – verify proper operation of fan power contactor (see
KV1/KV2 on electric diagram) and/or of pressure transducer (see BHP on electric
diagram) – (Air-Cooled).
2. Ambient temperature is too low - restore nominal conditions (Air-Cooled).
3. Air flows through the condenser even with fan off – protect dryer against wind or
external air flows (not caused by dryer’s fan) (Air-Cooled).
4. The temperature of the cooling water is too low – restore nominal conditions
(Water-Cooled).
5. The cooling water flow adjusting valve requires re-adjusting - contact a specialized
technician to restore nominal setting (Water-Cooled).
6. Refrigerant gas leak - contact a refrigeration engineer.
7. Compressor does not work – see specific point.
Summary of Contents for 1500-2500
Page 17: ...Technical data ACT 600 5000 17 EN 6 Technical data 6 1 Technical data ACT 600 5000 3 460 60 ...
Page 18: ...Technical data 18 EN ACT 600 5000 6 2 Technical data ACT 600 5000 3 575 60 ...
Page 38: ...Maintenance troubleshooting spare parts and dismantling 38 EN ACT 600 5000 ...
Page 41: ...Attachments ACT 600 5000 41 EN 9 1 Dryers dimensions 9 1 1 ACT 600 1250 ...
Page 42: ...Attachments 42 EN ACT 600 5000 9 1 2 ACT 1500 2500 ...
Page 43: ...Attachments ACT 600 5000 43 EN 9 1 3 ACT 3000 3750 ...
Page 44: ...Attachments 44 EN ACT 600 5000 9 1 4 ACT 4000 5000 ...
Page 45: ...Attachments ACT 600 5000 45 EN 9 2 Exploded views 9 2 1 ACT 600 1250 Air Cooled ...
Page 46: ...Attachments 46 EN ACT 600 5000 9 2 2 ACT 600 1250 Water Cooled ...
Page 47: ...Attachments ACT 600 5000 47 EN 9 2 3 ACT 1500 2500 Air Cooled ...
Page 48: ...Attachments 48 EN ACT 600 5000 9 2 4 ACT 1500 2500 Water Cooled ...
Page 49: ...Attachments ACT 600 5000 49 EN 9 2 5 ACT 3000 3750 Air Cooled ...
Page 50: ...Attachments 50 EN ACT 600 5000 9 2 6 ACT 3000 3750 Water Cooled ...
Page 51: ...Attachments ACT 600 5000 51 EN 9 2 7 ACT 4000 5000 Air Cooled ...
Page 52: ...Attachments 52 EN ACT 600 5000 9 2 8 ACT 4000 5000 Water Cooled ...
Page 66: ...Blank pages 66 EN ACT 600 5000 10 Blank pages ...