Technical description
ACT 600 – 5000
23 – EN
7.13 Refrigerant pressure switches LPS – HPS
As operation safety and protection of the dryer a series of pressure switches are installed in the gas circuit.
LPS :
Low-pressure protection device on the suction side of the compressor, trips if the pressure drops
below the pre-set value. The values are automatically reset when the nominal conditions are
restored.
Calibrated pressure :
R 407 C Stop 24.7 psig (1.7 barg) - Restart 53.7 psig (3.7 barg)
HPS :
This high-pressure controller device, located on the discharge side on the compressor, is activated
when the pressure exceeds the pre-set value. It features a manual-resetting button mounted on the
controller itself.
Calibrated pressure :
R 407 C Stop 435 psig (30 barg) - Manual reset P<334 psi (P<23 bar)
7.14 Compressor crankcase heater
At low temperatures oil can more easily be mixed with the refrigerant gas. So, when the compressor starts,
oil can be drawn into the refrigeration circuit and liquid hammering could occur.
To prevent this, an electrical resistance heater is installed in the suction side of the compressor. When the
system is powered and the compressor is not running, this heater keeps the oil at the correct temperature.
This heater is controlled by a thermo switch which prevents overheating the oil.
NOTE : The heater must be powered at least a couple of hours before the start up of the refrigeration
compressor.
Summary of Contents for 1500-2500
Page 17: ...Technical data ACT 600 5000 17 EN 6 Technical data 6 1 Technical data ACT 600 5000 3 460 60 ...
Page 18: ...Technical data 18 EN ACT 600 5000 6 2 Technical data ACT 600 5000 3 575 60 ...
Page 38: ...Maintenance troubleshooting spare parts and dismantling 38 EN ACT 600 5000 ...
Page 41: ...Attachments ACT 600 5000 41 EN 9 1 Dryers dimensions 9 1 1 ACT 600 1250 ...
Page 42: ...Attachments 42 EN ACT 600 5000 9 1 2 ACT 1500 2500 ...
Page 43: ...Attachments ACT 600 5000 43 EN 9 1 3 ACT 3000 3750 ...
Page 44: ...Attachments 44 EN ACT 600 5000 9 1 4 ACT 4000 5000 ...
Page 45: ...Attachments ACT 600 5000 45 EN 9 2 Exploded views 9 2 1 ACT 600 1250 Air Cooled ...
Page 46: ...Attachments 46 EN ACT 600 5000 9 2 2 ACT 600 1250 Water Cooled ...
Page 47: ...Attachments ACT 600 5000 47 EN 9 2 3 ACT 1500 2500 Air Cooled ...
Page 48: ...Attachments 48 EN ACT 600 5000 9 2 4 ACT 1500 2500 Water Cooled ...
Page 49: ...Attachments ACT 600 5000 49 EN 9 2 5 ACT 3000 3750 Air Cooled ...
Page 50: ...Attachments 50 EN ACT 600 5000 9 2 6 ACT 3000 3750 Water Cooled ...
Page 51: ...Attachments ACT 600 5000 51 EN 9 2 7 ACT 4000 5000 Air Cooled ...
Page 52: ...Attachments 52 EN ACT 600 5000 9 2 8 ACT 4000 5000 Water Cooled ...
Page 66: ...Blank pages 66 EN ACT 600 5000 10 Blank pages ...