90
ACK40A/AWSS40A
Cooling Only (R22)
Indoor, DB
Indoor, WB
Capacity
(°C)
(°C)
(kW)
13
20
25
30
35
40
45
TC
11.29
10.81
10.46
10.11
9.56
9.00
8.44
SC
11.05
10.60
10.28
9.96
9.45
8.94
8.43
TC
11.72
11.20
10.82
10.45
9.83
9.21
8.59
SC
10.13
9.79
9.55
9.31
8.93
8.55
8.18
TC
12.29
11.72
11.31
10.90
10.20
9.50
8.79
SC
8.90
8.69
8.55
8.50
8.22
8.02
7.84
TC
12.42
11.91
11.55
11.19
10.53
9.87
9.21
SC
8.16
7.97
7.84
7.71
7.53
7.35
7.18
TC
12.84
12.51
12.28
12.05
11.52
10.98
10.45
SC
6.02
5.90
5.81
5.73
5.57
5.42
5.27
TC
12.97
12.71
12.53
12.34
11.85
11.36
10.86
SC
5.33
5.23
5.17
5.10
4.95
4.80
4.65
15.5
17
Entering Water Temperature, (°C)
27.0
19
20
23
24
Water Flow Rate = 2.39 m
3
/hr
ACK50A/AWSS50A
Cooling Only (R22)
Indoor, DB
Indoor, WB
Capacity
(°C)
(°C)
(kW)
13
20
25
30
35
40
45
TC
14.03
13.43
12.99
12.56
11.87
11.18
10.48
SC
13.73
13.17
12.77
12.37
11.74
11.10
10.47
TC
14.56
13.91
13.44
12.98
12.21
11.44
10.67
SC
12.58
12.16
11.86
11.57
11.09
10.62
10.16
TC
15.26
14.55
14.05
13.54
12.67
11.80
10.92
SC
11.05
10.80
10.62
10.70
10.21
9.97
9.74
TC
15.43
14.80
14.35
13.90
13.08
12.26
11.44
SC
10.14
9.90
9.74
9.58
9.35
9.13
8.92
TC
15.95
15.55
15.26
14.97
14.31
13.64
12.98
SC
7.48
7.33
7.22
7.11
6.92
6.73
6.55
TC
16.12
15.79
15.56
15.33
14.72
14.11
13.49
SC
6.62
6.50
6.42
6.34
6.15
5.96
5.78
Entering Water Temperature, (°C)
27.0
19
20
23
24
15.5
17
Water Flow Rate = 2.82 m
3
/hr
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5°C
ACK30A/AWSS30A
Cooling Only (R22)
Indoor, DB
Indoor, WB
Capacity
(°C)
(°C)
(kW)
13
20
25
30
35
40
45
TC
9.05
8.66
8.38
8.10
7.65
7.21
6.76
SC
8.85
8.49
8.23
7.98
7.57
7.16
6.75
TC
9.39
8.97
8.67
8.37
7.87
7.38
6.88
SC
8.11
7.84
7.65
7.46
7.15
6.85
6.55
TC
9.84
9.38
9.06
8.73
8.17
7.60
7.04
SC
7.13
6.96
6.85
6.20
6.58
6.43
6.28
TC
9.95
9.54
9.25
8.96
8.43
7.90
7.37
SC
6.53
6.38
6.28
6.18
6.03
5.89
5.75
TC
10.28
10.02
9.84
9.65
9.23
8.80
8.37
SC
4.82
4.72
4.66
4.59
4.46
4.34
4.22
TC
10.39
10.18
10.03
9.89
9.49
9.09
8.70
SC
4.27
4.19
4.14
4.09
3.96
3.85
3.73
Entering Water Temperature, (°C)
27.0
19
20
23
24
15.5
17
Water Flow Rate = 1.75 m
3
/hr
Summary of Contents for AWSS30A
Page 1: ...Technical Manual WATER COOLED SINGLE SPLIT AWSS30A AWSS40A AWSS50A AWSS60A...
Page 13: ...13 Refrigerant Circuit Diagrams Model AWSS 30 40 50 60A...
Page 63: ...107 Indoor Unit MODEL ACC30C Outdoor Unit MODEL AWSS30A 10 WIRING DIAGRAMS...
Page 64: ...108 Indoor Unit Model ACC40 50 60C Outdoor Unit Model AWSS40 50 60A...
Page 65: ...110 Indoor Unit Model ACK30A Outdoor Unit MODEL AWSS30A...
Page 66: ...111 Indoor Unit Model ACK40 50A Outdoor Unit MODEL AWSS40 50A...