Acromag, Inc. Tel: 248-295-0880
- 36 -
Model SP33X-0700
4-Wire DC I/V Signal Splitter w/USB
Environmental...continued
Shock & Vibration Immunity:
Conforms to: IEC 60068-2-6: 10-500 Hz, 4G, 2
Hours/axis, for sinusoidal vibration; IEC 60068-2-64: 10-500 Hz, 4G-rms, 2
Hours/axis, for random vibration, and IEC 60068-2-27: 25g, 11ms half-sine, 18
shocks at 6 orientations, for mechanical shock.
Installation Category:
Suitable for installation in a Pollution Degree 2
environment with an Installation Category (Over-voltage Category) II rating per
IEC 1010-1 (1990).
Electromagnetic Compatibility (EMC)
Minimum Immunity per BS EN 61000-6-1:
1)
Electrostatic Discharge Immunity (ESD), per IEC 61000-4-2.
2)
Radiated Field Immunity (RFI), per IEC 61000-4-3.
3)
Electrical Fast Transient Immunity (EFT), per IEC 61000-4-4.
4)
Surge Immunity, per IEC 61000-4-5.
5)
Conducted RF Immunity (CRFI), per IEC 61000-4-6.
This is a Class B Product with Emissions per BS EN 61000-6-3:
1)
Enclosure Port, per CISPR 16.
2)
Low Voltage AC Mains Port, per CISPR 14, 16.
3)
DC Power Port, per CISPR 16.
4)
Telecom / Network Port, per CISPR 22.
Agency Approvals
Electromagnetic Compatibility (EMC
): CE Marked, per EMC Directive 2014/30/EU.
FCC Conformity:
This device complies with Part 15, Class B of the FCC rules.
Safety Approvals:
UL Listed (USA & Canada). Hazardous Locations
–
Class I, Division
2, Groups A, B, C, D Hazardous Location or Nonhazardous Locations only. These
devices are open-type devices that are to be installed in an enclosure suitable for
the environment.
ATEX / IECEx Certified:
The SP33x-0700 models are ATEX / IECEx Certified for
Explosive Atmospheres per ATEX Directive 2014/34/EU which complies with standards
IEC 60079-0 Edition 6, IEC 60079-15 Edition 4, EN 60079-0:2012+A11:2013, and
EN 60079-15:2010.
II 3 G Ex nA IIC T4 Gc -40
o
C ≤ Ta ≤ +75
o
C,
DEMKO 18 ATEX 2086
X
IECEx UL 18.0092
X
X
= Special Conditions
1)
The equipment shall only be used in an area of not more than pollution degree
2, as defined in EN/IEC 60664-1.
2)
The equipment shall be installed in an enclosure that provides a degree of
protection not less than IP 54 and only accessible with the use of a tool in
accordance with EN/IEC 60079-15.
3)
Transient protection shall be provided set to a level not exceeding 140 % of the
peak rated voltage value at the supply terminals to the equipment.
Reliability Prediction
Reliability Prediction
MTBF (Mean Time Between Failure):
MTBF in hours using MIL-HDBK-217F, FN2.
Per
MIL-HDBK-217, Ground Benign, Controlled, G
B
G
C