Model SP33X-0700
4-Wire DC I/V Signal Splitter w/USB
Quick Overview
–
Windows
Click
“Open”
to connect to the SP336-0700 and your
screen will like:
HELP
–
You can press F1 for Help on a selected or highlighted
field or control. You can also click the [?] button in the upper-
right hand corner of the screen and then click again to point
to a field or control to get a Help message pertaining to the
item you pointed to.
This transmitter can be
configured and calibrated via its
USB Configuration Software and
a USB connection to your
Windows PC or laptop. The USB
software can be downloaded
free of charge from our web site at
and
included on a CDROM bundled with the
Configuration Kit TT-SIP (see Accessories section). For
this model, look for the program SP33XConfig.exe. This
software is compatible with v7 or later versions of the
Windows operating system.
The initial USB configuration software screen for this
model is shown at left. Configuration information is
divided across three separately tabbed pages as follows:
Communication Set up, I/O Config/Test, and Calibration.
A short description of each of these configuration pages
follows:
Communication Set up (First Connect to Unit Here)
•
Select from connected transmitters and Open/Close
communication with them.
•
Display the Model, Serial Number, and Manufacturer
of the connected transmitter and report the status
of communication with it.
This section is used to select a connected transmitter,
and open/close communication with it. Device
connection Status is also indicated here, along with the
connected transmitter’s ID info (Product Name/serial,
Manufacturer, & Serial Number).
I/O Config/Test (Configure and/or Test the Unit Here)
•
You can click the
[Get I/O Config]
button to retrieve
the I/O configuration of the currently connected
transmitter.
•
Select the Input Range. You can select current
ranges ±20mA, 0-20mA, 4-20mA, 0-11.17mA, or
±1mA for current wired to TB1, or voltage ranges
±0.5V and 0-500mV for voltage wired to TB2.
•
Set the level of digital filtering to High, Medium,
Low, or None (No digital filter). The corresponding
I/O response time varies with filter selection and is
indicated in parenthesis next to your selection.
•
Set the Output Range to ±10V, ±5V, 0-5V, 0-10V,
±20mA, 0-20mA, or 4-20mA.
•
View the unit’s configur
ation message status in the
Status field.