60
Case Material:
Self-extinguishing NYLON type 6.6 polyamide thermoplastic
UL94 V-2, color beige; general purpose NEMA Type 1 enclosure.
Printed Circuit Boards:
Military grade FR-4 epoxy glass.
Shipping Weight:
1 pound (0.45 Kg) packed.
Safety Approvals:
CE marked (EMC Directive 2004/108/EC), UL Listed
(UL508-17th Edition, ANSI/ISA 12.12.01-2007), cUL Listed (Canada
Standard C22.2, Nos. 142-M1987 & 213-M1987), Hazardous Locations:
Class I; Division 2; Groups A, B, C, D.
Safety Approvals (989EN-4C16):
CE
marked (EMC Directive
2004/108/EC)
ATEX Certified:
Assessment by TUV Rheinland of North of America, Inc.
per
ATEX Directive 94/9/EC.
Ex nA IIC T4 Gc
TUVNA 14 EX 0001X
x = Special Conditions
1)
“WARNING-EXPLOSION HAZARD-DO NOT MAKE OR BREAK
CONNECTIONS IN HAZARDOUS LOCATIONS OR AREAS”
2)
“Warning: Must be installed in suitable enclosure with an Ingress
Protection of IP54 minimum,
in Hazardous Locations or Areas”
Operating Temperature (989EN-4016):
-40
C to +65
C (-40
F to +149
F).
Operating Temperature (989EN-4C16):
0
C to +55
C (+32
F to +131
F).
Storage Temperature (989EN-4016):
-40
C to +85
C (-40
F to +185
F).
Storage Temperature (989EN-4C16):
0
C to +70
C (+32
F to +158
F).
Relative Humidity:
5 to 95%, non-condensing.
Power Requirements:
18-36V DC SELV (Safety Extra Low Voltage).
Observe proper polarity. See table for current.
Supply
989EN-4016 Current Draw
18V
66mA Typical, 73mA Maximum
24V
49mA Typical, 55mA Maximum
36V
33mA Typical, 37mA Maximum
CAUTION:
Risk of Electric Shock
– More than one disconnect switch may
be required to de-energize equipment before servicing.
Isolation:
I/O channel, power, and network circuits are isolated from each
other for common-mode voltages up to 250VAC, or 354V DC off DC
power ground, on a continuous basis (will withstand 1500VAC dielectric
strength test for one minute without breakdown). Complies with test
requirements of ANSI/ISA-82.01-1988 for voltage rating specified.
Installation Category:
Designed to operate in an installation in a Pollution
Degree 2 environment with an installation category (over-voltage
category) II rating.
Electromagnetic Interference Immunity (EMI):
Inputs/outputs have
demonstrated resistance to inadvertent state changes with interference
from switching solenoids, commutator motors, and drill motors.
SPECIFICATIONS
Enclosure and Physical
Agency Approvals
Environmental
CAUTION: Do not exceed
36VDC peak, to avoid damage
to the module.
External Fuse: Select a high
surge tolerant fuse rated for 1
Amp or less to protect unit.
Note: Current draw does not
include excitation current
draw
.
Note that I/O channels are not
isolated channel-to-channel.