2
Extensions
MD82
8 digital 2 digital outputs with changeover contacts (8DI+2DO)
MLOG
TF card storage (alarm records, event records, electrical parameters and energy timing records, etc.)
MA84
8 analog inputs (class 0.5) + 4 analog outputs (class 0.5) (8AI+4AO)
MCM
1 RS485/Modbus-RTU, support master mode or slave mode
MCP
1 Profibus-DP
,
Configure this function to give MCM function, referred to as MCMP for short.
MCE
1 Ethernet, support Modbus-TCP, http, SMTP, DHCP protocol
,
Configure this function to give MCM
function, referred to as: MCME
Note:When selecting the extended function, the meter can take up to 3 modules. The modules can be the same or different, but
MCP\MCE\MLOG cannot select multiple identical modules combined, MCP and MCE only Can choose one. The installation sequence
can be arbitrary. If Ethernet or Profibus function is recommended for installation, it is recommended to install it near the A of the main
body. For the location of A, please refer to 3.3 Assembly.
2.2 Technical Parameters
display
Display method
Dot matrix LCD
;
Resolution
192 * 160
;
Backlight
White
LED
;
Visible area
69mm*62mm(2.8
Inch
/ 6.6
6inch
)
Signal
Electrical network
Three-phase three-wire, three-phase four-wire, see the wiring diagram;
Frequency
45
~
65Hz
;
Voltage
Rated value
:
AC 3*57.7/100V
、
AC 3*63.5/110V
、
AC 3*230/400V
、
AC
3*400/690V
;
690V direct connection on voltage input terminal
(
L-L
)
Overload
:
1.2 times rated value(continuous); 2 times rated value /1
second;
Power consumption: < 0.5VA (per channel);
Current
Rated value
:
AC 3x 1 (1.2) A
、
AC 3x5(6)A
,
support 4 mm
2
line access
;
Overload
:
1.2 times rated value(continuous); 10 times rated value/1 second;
Power consumption: < 0.5VA (per channel);
Measurement
accuracy
Voltage
、
current
IEC 61557-12
class 0.2
Voltage imbalance
IEC 61557-12
class 0.2
Voltage
harmonics,
current harmonics
IEC 61557-12
class 2
(
Note
1
)
frequency
IEC 61557-12
class 0.2s
Active power
IEC 61557-12
class 0.2s
Reactive power
IEC 61557-12
class 1s
inspecting power
IEC 61557-12
class 0.2
Active energy
IEC 62053-22 - Active energy0.2S
Reactive energy
IEC 62053-24 - Reactive energy0.5S
Power Quality
Recording wave
20 waveforms, 10 waves before and after;