24
1st check digit
No parity, 2 stop bits, odd parity, even parity
2nd baud rate
1200
,
2400
,
4800
,
9600
,
19200
,
38400
2nd check digit
No parity, 2 stop bits, odd parity, even parity
Profibusaddress
1~126
DLT645 address
0~999999999999
DLT645 Leader
Add None(No preamble)
、
Add 4 0xfc(Add 4 0xFC)
Automatic acquisition IP
Close, open
Modbus TCP port
1~59999
IP address
000.000.000.000
(
If the expansion module MCE is not configured, the default
is 0. If the force expansion module MCE is configured, it is 192.168.8.150.
)
Subnet mask
000.000.000.000
(
If the expansion module MCE is not configured, the default
is 0. If the force expansion module MCE is configured, it is 255.255.255.0.
)
Default gateway
000.000.000.000
(
If the expansion module MCE is not configured, the default
is 0. If the force expansion module MCE is configured, it is 192.168.8.1.
)
6.4 Alarm Settings
On the main interface, press Menu to enter the menu interface, press
∨
until
“
Parameter Setting
”
is
highlighted, and press
√
to enter the parameter setting interface. Press
∨
until
“
Alarm Setting
”
is highlighted,
press
√
to enter the alarm setting interface. Press
∧
or
∨
to switch the item of alarm setting, press Enter to enter
the setting of the item, press + or - to change, press > to shift, after the current item setting is changed, press Exit to
exit the item setting. Continue to repeat the above steps to modify the settings. After the change is completed, press
Exit to enter the password. The default password is 0001 (customer can change the password according to the
password setting set by 7.11 system. If you forget the password, you need to contact us). Press SaveExit to save the
changes and exit, press Esc to exit without saving the changes.
Alarm type reference 5.1.2 View alarm table 1: Alarm classification description
Setting up projects
Range
Explain
Alarm 1 types
Refer to 5.1.2 View Alarm Table 1: Alarm
Classification Description
Alarm switch
Open close
Turn alarms on or off
Action threshold
-9999~9999
Alarm action value, unit and decimal point
position are consistent with the meter display