63
Connect the Ethernet module and the computer with a twisted-pair B cable, power the meter. If the local connection on the bottom
right corner of the computer monitor is connected at this point, you can continue to the next step. Otherwise, power off the meter, check
the network cable and network settings.
2
、
WEB page configuration
Open Internet Explorer, enter the Ethernet IP address in the address bar (http://192.168.1.150/, factory default setting), and the
login screen shown in the figure below will appear.
Click Setup to enter the Ethernet & TCP/IP configuration interface, as shown below:
After the modification is completed, click Apply to wait for it to take effect.
8.2
Extension of RS485 Communication
Extended 485 communication does not support the DLT-645 protocol and only supports the Modbus-RTU protocol.
8.2.1
Extending RS485 Communication as a Modbus Slave Station
When the second communication serves as a slave station, as the first channel RS485 communication, only supports the 0x03
command and does not support the 0x10 command. Refer to Chapter 8 for the address table.
8.2.2 Modbus_TCP communication (Using ModScan software)
When using the Ethernet Modbus_TCP protocol, it supports 0x01 (read coil status), 0x02 (read input status), 03 (read hold register),
0x05 (write single coil). (Note: When using the 01, 02, and 05 commands, they all correspond to the APM8xx meter's own information.
DI1 and DO1 correspond to the starting address 0.)