![Acrel APM830 Installation And Operation Instruction Manual Download Page 51](http://html1.mh-extra.com/html/acrel/apm830/apm830_installation-and-operation-instruction-manual_2841076051.webp)
46
Other event records: Refer to event record 1
2204
Event record 2
2208
Event record 3
2212
Event record 4
2216
Event record 5
2220
Event record 6
2224
Event record 7
2228
Event record 8
2232
Event record 9
2236
Event record 10
2240
Event record
11
2244
Event record
12
2248
Event record
13
2252
Event record 14
2256
Event record 15
2260
Event record
16
Note: To read the most recent 128 event records, you can read the register 20000-20513, refer to the format of register 2200-2203.
Other recent alarm records: Refer to recent alarm record 1
2306
Alarm record 2
2312
Alarm record 3
2318
Alarm record 4
2324
Alarm record 5
2330
Alarm record 6
2336
Alarm record 7
2342
Alarm record 8
2348
Alarm record 9
2354
Alarm
record
10
2360
Alarm
record
11
2366
Alarm record
12
2372
Alarm record
13
2378
Alarm
record
14
2384
Alarm
record
15
2390
Alarm
record
16
Classification of alarm records (16 for each type of alarm, polling display, latest record covers the earliest record automatically): Refer to
recent alarm record 1 for data format.
10000-10767
Overcurrent alarm (16 in total, the same below)
10768-11535
Undercurrent alarm event
11536-12303 Overvoltage alarm event
12304-13071 Undervoltage alarm event
13072-13839 Overpower alarm event
13840-14607 Underpower alarm event
14608-15375 Demand alarm event
Low byte indicates DI/DO number
。
2201
Year
、
Month
UInt16
(RO)
High byte:Year; Low byte: Month
2202
Day
、
Hour
UInt16
(RO)
High byte: Day ; Low byte: Hour
2203
Minute
、
second
UInt16
(RO)
High byte:Year; Low byte:Second
Register
(WORD)
Description
Unit
Data Type
Note
2300
Recent alarm
record 1
Alarm type
UInt16 (RO)
High byte: Alarm group; Low byte: Alarm
type (refer to 7.4 to view alarms -
Communication
number
of
alarm
classification description)
2301
Year
、
Month
UInt16 (RO)
High byte: Year; Low byte: Month
2302
Day
、
Hour
UInt16 (RO)
High byte: Day ; Low byte: Hour
2303
Minute
、
second
UInt16 (RO)
High byte:Year; Low byte: Month
2304
Alarm value
UInt16 (RO)
Primary
2305
Alarm status
UInt16 (RO)
1: Alarm acts 0: Alarm released