Page B-2
−
In RS422 multipoint slave mode or in RS485 mode, the RTS/DTR lamp
remains off.
Check the configuration of SW2, transmission validation by either RTS or DTR.Check that
the serial driver correctly handles the RTS or DTR signal (see the signal-timing
diagram on page 2-5 ). If not, generate the RTS signal with a shunt (configuration n°1
or n°2 on pages 2-7 and 2-8 ), or use the xxMI400/RTS model with automatic
transmission control.
−
In RS422 multipoint slave mode or in RS485 mode, numerous transmission
errors.
Check the line bias, only one bias per line is required.
−
The lamps operate normally, but no correct replies.
Check the cabling on the RS422A/RS485 connector.
Check the bias of the RS422A/RS485 signals in the idle state. In an idle state, the +TX and
+RX differential signals are at a lower potential than the -TX and -RX signals. This
remark is particularly important when connecting other RS422A-RS485
interfaces. In effect, there is considerable confusion concerning the idle state in
which the line should be found, and concerning the names for sTX, +RX, -
TX and -RX (A, A', B and B') in the various interfaces of different manufacturers.
Summary of Contents for MI400 Series
Page 2: ......
Page 6: ...NOTES ...
Page 16: ...NOTES ...
Page 17: ...SECTION 2 MI400 Series MI400 RKMI400 MI400 24V ...
Page 18: ...NOTES ...
Page 29: ...SECTION 3 MI400 RTS Series MI400 RTS MI400 24V RTS RKMI400 RTS ...
Page 30: ...NOTES ...
Page 40: ...NOTES ...
Page 41: ...SECTION 4 MI400 400 Series MI400 400 ...
Page 42: ...NOTES ...
Page 47: ...SECTION 5 Assembly Examples With FIXING PLATE RDMI RKMI ...
Page 48: ...NOTES ...
Page 54: ...NOTES ...
Page 55: ...SECTION 6 Temperature Tests ...
Page 56: ...NOTES ...
Page 60: ...NOTES ...
Page 61: ...APPENDIX A Distribution Signals ...
Page 62: ...NOTES ...
Page 65: ...APPENDIX B Troubleshooting ...
Page 66: ...NOTES ...
Page 69: ...APPENDIX C Extract from EIA standard Cable length ...
Page 70: ...NOTES ...
Page 78: ......
Page 79: ......