background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 3

Version: 6.0

I0000586

Note:

 The ARM2 does NOT isolate the input signals from the 

output signals. Use the Analog Isolation Module (AIM1, AIM2) 
if you need to isolate the input signals from output signals.

FACTORY CALIBRATION

The ARM2 is set as follows:

• No Attenuation to the Input Signal
• Voltage Input Signal
• Current Output Signal
• Normal Acting Output Signal
• No Offset to the Output Signal
• Gain of 1 to the Output Signal (1:1). All four (4) pots should 
be full counterclockwise (you can check them as they may 
make a slight clicking sound at the end of their range).

The ARM2 can be ordered calibrated to your specifications or you may follow the procedure below to set                        
your own calibration.

Be sure to check the input, output, GAIN and OFFSET specifications of the ARM2. It is possible that the 
ARM2 cannot re-scale to your requirements.

Calibration

Complete the following steps to change the calibration of the ARM2. You will need a digital volt/current 
meter, a 24 VDC power supply and a voltage input signal simulator. (A 5K ohm or greater trim pot can be 
used as a voltage input signal simulator by connecting one end of the trim pot resistance winding to the 
(+) 24 of the power supply, the other end of the trim pot resistance winding to the (-) 24 of the power 
supply and the wiper end of the trim pot to the “IN” terminal of the ARM2).

EQUIVALENT CALIBRATION VOLTAGE

Use a voltage signal for your input signal during calibration:

 this makes both the procedure and the 

explanation easier. If you will require a current input when you are finished, use the equation below to find 
the equivalent calibration voltage to use during the calibration procedure:

Equivalent Calibration Voltage = Required Input Signal Amps x 250

Example: 

1 VDC is the equivalent calibration voltage for a 4 milliamp input signal (1 = .004 x 250) or 5 

VDC is the equivalent calibration voltage for a 20 milliamp input signal (5 = .020 x 250).

Step 1)

 

Trim Pot Presets:

 

Set all pots as follows to start (These are 25 turn trim pots with no hard stops; they may make a slight 
clicking sound at either end of their 
range):

Turn the following pots full counter 
clockwise (25 turns): 
GAIN = gain of 1
OFFSET = 0 volts offset
REV = 0 volts reverse
ATTN = (no input signal attenuation)

Step 2) Jumper Shunt Presets
J1- NORMAL OR REVERSE ACTING:

 Set in “N” position for direct acting output signal. (If you require a 

reverse acting output signal, you will set this shunt in the “R” position in Step 7).

J2 - OFFSET:

 Set in the “O” position for no offset to the output. (If you will require a “+” or “-” offset, you will 

set this shunt in the appropriate position in Step 6).

J3 INPUT - INCOMING SIGNAL:

 Set in “E” position for voltage input . (If you require a current input, you 

will set this shunt in the “I” position AFTER you are finished with the calibration procedure).

Step 3) Wiring Connections

Make the following connections with the power OFF.
Connect a 24 volt AC or DC power supply to the ARM2 terminals “PWR” (+) and “PWR” (-).
Connect the input signal common (-) to the “SIG IN” (-) terminal. Connect (+) input signal lead to the “SIG IN” 
(+) terminal. To read input signal at ARM2 terminals connect (+) meter lead to the “SIG IN” (+) terminal and 
the (-) meter lead to the “SIG IN” (-) terminal (or in parallel).  To read mA signal on either output, connect the 
meter in series with connections to the SIG1 and SIG2 output terminals.  That is meter (+) to “SIG 1 or 2 OUT” 
(-) terminal and meter (-) to wire going to device being controlled.

Step 4) Power Up

Turn on the 24 volt power supply: the POWER indicator will light.

Step 5) Input/Output Signal Adjustments

In this step you will figure the desired voltage input signal span and the desired current output signal span 
(see the section on Equivalent Calibration Voltage) and calibrate the ARM2 to these input and output 
signal spans.

FIGURE 3:

 JUMPER SHUNTS

ACTION

J1

R

N

Jumper Shunt Detail

   (Shown)

Direct Acting

Selected

J2

OFFSET

O - +

 (Shown)

No Offset

Selected

J3

I E

INPUT

     (Shown)

Voltage Power

Input Selected

PWR

J4

DC AC

  (Shown)

DC Power

Selected

Summary of Contents for ANALOG INTERFACE Series

Page 1: ...be required Use only fingers to remove board from snap track Slide out of snap track or push against side of snap track and lift that side of the circuit board to remove Do not flex board or use tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect or disconnect wiring with power applied When using a shielded cable ground the shield only at the controller end Grounding bot...

Page 2: ...e sure to check the input output GAIN and OFFSET specifications of the ARM2 It is possible that the ARM2 cannot re scale to your requirements Calibration Complete the following steps to change the calibration of the ARM2 You will need a digital volt current meter a 24 VDC power supply and a voltage input signal simulator A 5K ohm or greater trim pot can be used as a voltage input signal simulator ...

Page 3: ... no offset to the output If you will require a or offset you will set this shunt in the appropriate position in Step 6 J3 INPUT INCOMING SIGNAL Set in E position for voltage input If you require a current input you will set this shunt in the I position AFTER you are finished with the calibration procedure Step 3 Wiring Connections Make the following connections with the power OFF Connect a 24 volt...

Page 4: ...s 8 to 16mA Adding an offset of 4mA will now make the output signal range 4 to 12mA Apply the minimum voltage input signal and read the minimum output signal on the meter With the OFFSET jumper shunt J2 in the O position from Step 6 no offset voltage will be added or subtracted from the output signal range If you need to shift the output signal range up set the OFFSET jumper shunt J2 in the positi...

Page 5: ...n input value Less than or equal to 1 of output span over full temperature range when using 1 1 input to output Accuracy is calibration dependent over full temperature range 0 to 100 0 25 to 20 VDC 20 to 0 mA nominal 750Ω 20 mA 23 VDC nominal 24 VAC Power Supply 30 mA maximum 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 ...

Page 6: ...NOTES Page 6 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 6 0 I0000586 ...

Page 7: ...NOTES Page 7 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 6 0 I0000586 ...

Page 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 6 0 I0000586 ...

Reviews: